YSLYCY-JZ

YSLYCY-JZ                                                                        

       

Cross Section Conductor Resistance
(Max. Ω/km)
0.50 mm² 39.0
0.75 mm² 26.0
1.00mm² 19.5
1.50 mm² 13.3
2.50 mm² 7,98
Technical and Electrical Properties (20°C)
Operating Voltage 0.50 mm² ... 1.50 mm² 300V/500V
  2.50mm²............... .. 450V/ 750V
Test Voltage 2500V  
Insulation Resistance Min. 200 M.Ohm x Km  
Current Carrying Capacity See Technical Data Table 4  
Temperature Range Fixed -30°C .. + 70°C
  Flexible -5°C . . + 70°C
Minimum Bending Radius Fixed 10x Cable Diameter
  Flexible 20 x Cable Diameter
X: For JZ types with Yellow I Green marked earthing core 2: for OZ types without earthing core 1
4.00 mm² and 6.00 mm² cross sections are also available for YSLYCY·JZ cables.
PART NUMBER NO OF CORES/CROSS SECTION (mm² ) CABLE DIAMETER (mm) COPPER WEIGHT (Kg/Km) CABLE WEIGHT (Kg/Km)
0.50mm²    
34x00502 2x0.50 6.8 20.3 67
34x00503 3x0.50 7.0 24.9 77
34x00504 4x0.50 7.9 31.8 92
34x00505 5x0.50 8.4 37.4 104
34x00506 6x0.50 8.9 42.6 116
34x00507 7x0.50 8.9 46.9 128
34x00508 8x0.50 9.8 53.6 143
34x00509 9x0.50 10.4 58.7 159
34x00510 10x0.50 11.0 65.2 176
34x00512 12x0.50 11.3 74.7 207
34x00515 15x0.50 12.8 90.1 245

34x00516

16x0.50

12.8 94.3 257

34x00519

19x0.50

13.3 106.4 295

34x00520

20x0.50

14.0 122.5 309

34x00521

21x0.50

14.0 126.8 320

34x00525

25x0.50

15.3 148.9 373

34x00527

27x0.50

15.8 159.0 392

34x00530

30x0.50

16.2 174.4 425
         

0.75mm²

 
34x00802 2x0.75 7.2 26.8 76
34x00803 3x0.75 7.6 35.7 92
34x00804 4x0.75 8.2 44.2 110
34x00805 5x0.75 9.1 51.9 131
34x00806 6x0.75 9.8 61.4 149
34x00807 7x0.75 9.8 67.9 159
34x00808 8x0.75 10.4 76.7 184
34x00809 9x0.75 11.1 84.5 209
34x00810 10x0.75 12.0 93.3 234
34x00812 12x0.75 12.5 108.3 260

34x00815

15x0.75

13.8 139.9 311

34x00816

16x0.75

13.8 146.4 325

34x00819

19x0.75

14.6 169.2 382

34x00820

20x0.75

15.3 178.5 403

34x00821

21x0.75

15.3 185.5 415

34x00825

25x0.75

16.9 217.2 490

34x00827

27x0.75

17.4 237.2 522

34x00830

30x0.75

18.1 255.5 590
       
Download PDF

 
               ABU DHABI                  DUBAI                       JAFZA                                                 MUSCAT                                                   DOHA

UAE +971 2 5557351    +971 4 3352995    +971 4 8831401        OMAN  +968 24 750205        QATAR   +974 44150543

PART NUMBER NO OF CORES/CROSS SECTION (mm² ) CABLE DIAMETER (mm) COPPER WEIGHT (Kg/Km) CABLE WEIGHT (Kg/Km)

1.00mm²

 
34x01002 2x1.00 7.9 34.0 92
34x01003 3x1.00 8.3 44.2 108
34x01004 4x1.00 9.1 54.5 130
34x01005 5x1.00 10.0 64.2 158
34x01006 6x1,00 11.0 79.5 188
34x01007 7x1.00 11.0 86.5 199
34x01008 8x1.00 12.0 96.9 233
34x01009 9x1,00 12.9 109.8 266
34x01010 10x1.00 14.2 127.7 321
34x01012 12x1.00 14.5 147.9 353

34x01015

15x1.00

15.8 178.9 420

34x01016

16x1.00

15.8 187.9 426

34x01019

19x1.00

16.9 216.7 496

34x01020

20x1.00

17.9 230.9 543

34x01021

21x1.00

17.9 239.9 549

34x01025

25x1.00

19.6 283.4 667
         

1.50mm²

 
34x01502 2x1.50 8.6 44.4 113
34x01503 3x1.50 9.1 58.8 133
34x01504 4x1.50 10.0 75.0 164
34x01505 5x1.50 11.0 90.4 199
34x01506 6x1,50 12.1 112.0 240
34x01507 7x1.50 12.1 119.8 251
34x01508 8x1.50 13.1 140.6 291
34x01509 9x1,50 14.2 158.7 340
34x01510 10x1.50 15.2 177.5 386
34x01512 12x1.50 15.6 206.1 422

34x01515

15x1.50

17.4 251.3 521

34x01516

16x1.50

17.4 264.8 532

34x01519

19x1.50

18.6 301.5 615

34x01520

20x1.50

19.6 328.1 669
         

2.50mm²

 
34x02502 2x2.50 10.0 65.7 157
34x02503 3x2.50 10.6 89.3 189
34x02504 4x2.50 11.6 113.7 231
34x02505 5x2.50 13.0 144.0 291
34x02506 6x2.50 14.1 185.8 346
34x02507 7x2.50 14.1 192.8 361
34x02508 8x2.50 15.9 219.5 441
34x02509 9x2.50 16.8 245.4 493
34x02510 10x2.50 18.0 272.0 558
         

YSLYCY-JZ

Construction  
Conductor Stranded Electrolytic Annealed Copper (IEC 228/VDE0295/HD383/BS 6360 Class 5)
Insulation PVC (EN 50290-2/ HD 21 .1 .S4/VDE 0281-TI2). Color Code (VDE02931: Black (White numbered)
  After 3 cores there is number/green marked drain wire.
Lay-up All cores as layers
Inner Sheath PVC Color: RAL 7001 Grey
Screen Tinned Copper Wire Braiding (70% Coverage) (EN 50288)
Outer Sheath PVC (EN 50290-2/ HD 21.1.S4 /VDE 0281TM1) Outer Sheath Color : RAL7001 Grey
   
Reference Standards VDE 0245
Flame Test IEC60332-1, VDE 04B2-265-2-1

Applications
These type of cables which PVC sheathed and braiding screened are used in office equipment, electronic control systems, air condition systems. powerstations. engineering projects for control, vision and measurement purposes. They are very flexible due to the use of thin multicore copper as conductor. They can be used in wet or dry indoor applications but for outdoor use, UV protected PVC must be used where sunlight is abundant. Screening , protects the cable from the
outer electrical effects.