V – Varistor, screw terminals
- Single stage surge arrester
- Installation close to protected equipment
- For protection of signaling, data and other lines against impact of surge voltage
Specifications:
Parameter name |
Parameter value |
||
Type
of SPD |
C2 |
|
|
Location
of SPD |
ST 2 |
|
|
Mounting |
DIN rail 35 mm |
|
|
Maximum
operating voltage |
Uc |
140.00 V AC |
|
Maximum
operating voltage |
Uc |
180.00 V DC |
|
Nominal
load current |
IL |
16.000 A |
|
C2
nominal discharge current (8/20 µs) per core |
In |
6.00 kA |
|
C2
voltage protection level mode core-PE at In |
Up |
530 V |
|
Response
time core-PE |
ta |
25 ns |
|
Connection
(input - output) |
terminals-terminals |
|
|
Cross-section
of connected conductors solid (min) |
0.14 mm2 |
|
|
Cross-section
of connected conductors solid (max) |
4.00 mm2 |
|
|
Cross-section
of connected conductors stranded (min) |
0.14 mm2 |
|
|
Cross-section
of connected conductors stranded (max) |
2.50 mm2 |
|
|
Range
of ambient temperatures (min/max) |
-40 / 70 °C |
|
|
According
to standard |
EN 61643-21+A1,A2:2013, IEC
61643-21+A1,A2:2012 |
|
|
ETIM
Class |
EC000943 |
|
|
Customs
tariff number |
85363010 |
|
|
EAN |
8595090551515 |
|
Dimensions:
Single stage surge arrester – Varistor, screw terminal, 180 V DC
Related Product
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking.Two-pole high performance lightning curr..
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking, remote fault signalling.Combination of ..
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking.Combination of one-pole high performance..
Combined lightning current arrester,25 kA
Pluggable module, visual fault signalling, module locking, remote fault signalling.One-pole high p..