For general
structured cabling networks.
- Combined
(2-stage) SPD for general structured cabling networks.
- LPZ
0 to LPZ 1 boundary installation.
- To protect devices working with signals over twisted pairs up to 60 V.
Specifications:
Parameter name |
Parametervalue |
|||
Type
of SPD |
D1,C2,C3 |
|||
Location
of SPD |
ST 1+2+3 |
|||
Mounting |
DIN rail 35 mm |
|||
Maximum
operating voltage core-core |
Uc |
60,00 V DC |
||
Maximum
operating voltage pair-pair (POE) |
Uc |
60,00 V DC |
||
Nominal
load current per core at 25 °C |
IL |
0.5 A |
||
Treshold
frequency core-core |
f |
250.00 MHz |
||
Insertion
attenuation at treshhold frequency |
1.50 dB |
|||
C2
nominal discharge current (8/20 µs) core-core |
In |
0.15 kA |
||
D1
total discharge current (10/350 µs) cores-PE |
ITotal |
2.00 kA |
|
|
C2
total discharge current (8/20 µs) cores-PE |
ITotal |
10.00 kA |
||
C2
voltage protection level mode core-core (@Uoc/In) |
Up |
120,00 V (0,3 kV / 0,15 kA) |
||
C2
voltage protection level mode core-PE (@Uoc/In) |
Up |
700,00 V (2,5 kV / 1,25 kA) |
||
C2
voltage protection level mode pair-pair (POE) (@Uoc/In) |
Up |
90,00 V (0,3 kV / 0,15 kA) |
||
C3
voltage protection level mode core-core (@In - 1 kV/µs) |
Up |
110,00 V (10 A) |
||
C3
voltage protection level mode core-PE (@In - 1 kV/µs) |
Up |
500,00 V (10 A) |
||
C3
voltage protection level mode pair-pair (POE) (@In - 1 kV/µs) |
Up |
85,00 V (10 A) |
||
Response
time core-core |
ta |
1 ns |
||
Response
time core-PE |
ta |
100 ns |
||
Connection
(input - output) |
RJ 45/RJ 45 |
|||
Degree
of protection |
IP 30 (without connectors IP 10) |
|||
Range
of ambient temperatures (min/max) |
-10 / 50 °C |
|||
Humidity |
15 - 85 % |
|||
According
to standard |
EN 61643-21+A1,A2:2013, IEC
61643-21+A1,A2:2012 |
|||
ETIM
Class |
EC000943 |
|||
Customs
tariff number |
85363010 |
|||
EAN |
8595090570691 |
Dimensions:
SPD for general structured cabling networks,60 V, LPZ 0-1 and higher.
Related Product
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking.Two-pole high performance lightning curr..
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking, remote fault signalling.Combination of ..
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking.Combination of one-pole high performance..
Combined lightning current arrester,25 kA
Pluggable module, visual fault signalling, module locking, remote fault signalling.One-pole high p..