For high-speed
general structured cabling networks.
- Combined
(2-stage) SPD for high-speed general structured cabling networks.
- LPZ 0 to LPZ 1
boundary installation.
- To protect
devices working with signals over twisted pairs up to 60V.
Specifications:
Parameter name |
Parameter
value |
|
Type of SPD |
D1,C2,C3 |
|
Location of SPD |
ST
1+2+3 |
|
Mounting |
DIN
rail 35 mm |
|
Maximum operating voltage core-core |
Uc |
60,00
V DC |
Maximum operating voltage pair-pair
(POE) |
Uc |
60,00
V DC |
Nominal load current per core at 25
°C |
IL |
0.5
A |
Treshold frequency core-core |
f |
500.00
MHz |
Insertion attenuation at treshhold
frequency |
2.50
dB |
|
C2 nominal discharge current (8/20
µs) core-core |
In |
0.15
kA |
D1 total discharge current (10/350
µs) cores-PE |
ITotal |
2.00
kA |
C2 total discharge current (8/20 µs)
cores-PE |
ITotal |
10.00
kA |
C2 voltage protection level mode
core-core (@Uoc/In) |
Up |
120,00
V (0,3 kV / 0,15 kA) |
C2 voltage protection level mode
core-PE (@Uoc/In) |
Up |
700,00
V (2,5 kV / 1,25 kA) |
C2 voltage protection level mode
pair-pair (POE) (@Uoc/In) |
Up |
90,00
V (0,3 kV / 0,15 kA) |
C3 voltage protection level mode
core-core (@In - 1 kV/µs) |
Up |
110,00
V (10 A) |
C3 voltage protection level mode
core-PE (@In - 1 kV/µs) |
Up |
500,00
V (10 A) |
C3 voltage protection level mode
pair-pair (POE) (@In - 1 kV/µs) |
Up |
85,00
V (10 A) |
Response time core-core |
ta |
1
ns |
Response time core-PE |
ta |
100
ns |
Connection (input - output) |
RJ
45/RJ 45 |
|
Degree of protection |
IP
30 (without connectors IP 10) |
|
Range of ambient temperatures
(min/max) |
-10
/ 50 °C |
|
Humidity |
15
- 85 % |
|
According to standard |
EN
61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012 |
|
ETIM Class |
EC000943 |
|
Customs tariff number |
85363010 |
|
EAN |
8595090570707 |
Dimensions:
SPD for general structured cabling networks ,60V, LPZ 0-1 and higher
Related Product
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking.Two-pole high performance lightning curr..
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking, remote fault signalling.Combination of ..
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking.Combination of one-pole high performance..
Combined lightning current arrester,25 kA
Pluggable module, visual fault signalling, module locking, remote fault signalling.One-pole high p..