Coupling impedance (resistance), screw terminals
- Coarse and fine surge protection for 2-core signalling networks
- Installation close to protected equipment
- For protection of communication interfaces and measuring lines of I&C, electronic security and fire detection systems, etc. against impact of surge voltage
- Coarse and fine surge protection in differential mode (core – core) and coarse protection in common mode (core – PE)
Specifications:
Parameter name |
Parameter value |
|
Type of SPD |
C2,C3 |
|
Location of SPD |
ST 2+3 |
|
Mounting |
DIN rail 35 mm |
|
Nominal voltage |
Un |
60 V DC |
Maximum operating voltage |
Uc |
45.00 V AC |
Maximum operating voltage |
Uc |
64.00 V DC |
Nominal load current |
IL |
0.500 A |
Treshold frequency core-core |
f |
6.50 MHz |
Serial resistance per core |
R |
1.60 Ω |
D1 impulse discharge current (10/350 µs) per core |
Iimp |
0.50 kA |
D1 total discharge current (10/350 µs) cores-PE |
ITotal |
1.00 kA |
C2 nominal discharge current (8/20 µs) per core |
In |
5.00 kA |
C2 total discharge current (8/20 µs) cores-PE |
ITotal |
10.00 kA |
C2 voltage protection level mode core-PE at In |
Up |
350 V |
C2 voltage protection level mode core-core at In |
Up |
100 V |
C3 voltage protection level mode core-PE at 1 kV/µs |
Up |
500 V |
C3 voltage protection level mode core-core at 1 kV/µs |
Up |
85 V |
Response time core-core |
ta |
1 ns |
Response time core-PE |
ta |
100 ns |
Connection (input - output) |
terminals-terminals |
|
Cross-section of connected conductors solid (min) |
0.14 mm2 |
|
Cross-section of connected conductors solid (max) |
4.00 mm2 |
|
Cross-section of connected conductors stranded (min) |
0.14 mm2 |
|
Cross-section of connected conductors stranded (max) |
2.50 mm2 |
|
Degree of protection |
IP 20 |
|
Range of ambient temperatures (min/max) |
-40 / 70 °C |
|
According to standard |
EN 61643-21+A1,A2:2013,
IEC 61643-21+A1,A2:2012 |
|
ETIM Class |
EC001625 |
|
Customs tariff number |
85363010 |
|
EAN |
8595090551362 |
Surge protection for 2-core floating signalling networks, 60 V DC, max. 0.5 A
Related Product
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking.Two-pole high performance lightning curr..
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking, remote fault signalling.Combination of ..
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking.Combination of one-pole high performance..
Combined lightning current arrester,25 kA
Pluggable module, visual fault signalling, module locking, remote fault signalling.One-pole high p..