Coupling impedance (resistance), screw
terminals.
- Coarse and fine surge
protection for 2-core signalling networks.
- Installation close to
protected equipment.
- For protection of
communication interfaces and measuring lines of I&C, electronic security
and fire detection systems, etc. against impact of surge voltage.
- Coarse and fine surge protection in differential mode (core – core) and coarse protection in common mode (core – PE).
Specifications:
Parameter name |
Parameter value |
|
Type of SPD |
C2,C3 |
|
Location of
SPD |
ST 2+3 |
|
Mounting |
DIN rail 35 mm |
|
Nominal
voltage |
Un |
12 V DC |
Maximum
operating voltage |
Uc |
11.00 V AC |
Maximum
operating voltage |
Uc |
16.00 V DC |
Nominal
load current |
IL |
0.500 A |
Treshold
frequency core-core |
f |
2.00 MHz |
Serial
resistance per core |
R |
1.60 Ω |
D1 impulse
discharge current (10/350 µs) per core |
Iimp |
0.50 kA |
D1 total
discharge current (10/350 µs) cores-PE |
ITotal |
1.00 kA |
C2 nominal
discharge current (8/20 µs) per core |
In |
5.00 kA |
C2 total
discharge current (8/20 µs) cores-PE |
ITotal |
10.00 kA |
C2 voltage
protection level mode core-PE at In |
Up |
350 V |
C2 voltage
protection level mode core-core at In |
Up |
28 V |
C3 voltage
protection level mode core-PE at 1 kV/µs |
Up |
500 V |
C3 voltage
protection level mode core-core at 1 kV/µs |
Up |
20 V |
Response
time core-core |
ta |
1 ns |
Response
time core-PE |
ta |
100 ns |
Connection
(input - output) |
terminals-terminals |
|
Cross-section
of connected conductors solid (min) |
0.14 mm2 |
|
Cross-section
of connected conductors solid (max) |
4.00 mm2 |
|
Cross-section
of connected conductors stranded (min) |
0.14 mm2 |
|
Cross-section
of connected conductors stranded (max) |
2.50 mm2 |
|
Degree of
protection |
IP 20 |
|
Range of
ambient temperatures (min/max) |
-40 / 70 °C |
|
According
to standard |
EN 61643-21+A1,A2:2013,
IEC 61643-21+A1,A2:2012 |
|
ETIM Class |
EC001625 |
|
Customs
tariff number |
85363010 |
|
EAN |
8595090551331 |
Dimensions:
Surge protection for 2-core floating signalling networks, terminal block with screw terminals, 12 V DC, max. 0,5 A
Related Product
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking.Two-pole high performance lightning curr..
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking, remote fault signalling.Combination of ..
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking.Combination of one-pole high performance..
Combined lightning current arrester,25 kA
Pluggable module, visual fault signalling, module locking, remote fault signalling.One-pole high p..