• Surge protection for 2-core signalling lines, installation close to protected equipment, 48 V DC, max. 0,5 A

Coupling impedance (R – resistance)


  • Coarse and fine surge protection for 2-core signalling lines
  • Installation close to protected equipment
  • For protection of communication interfaces of I<(>&<)>C, electronic security and fire detection systems, etc. (mainly for RS-485 interfaces) against impact of surge voltage
  • Coarse and fine surge protection in differential mode (core – core) and common mode (core – PE)


Specifications

Parameter name

Parameter value

Type of SPD

D1,C1,C2,C3,B2

Location of SPD

ST 2+3

Mounting

DIN rail 35 mm

Nominal voltage

Un

48 V DC

Maximum operating voltage

Uc

35.60 V AC

Maximum operating voltage

Uc

50.20 V DC

Nominal load current

IL

0.500 A

Treshold frequency core-core

f

5.00 MHz

Serial resistance per core

R

1.00 Ω

D1 total discharge current (10/350 µs) cores-PE

ITotal

1.00 kA

C1 voltage protection level mode core-core

Up

85.00 V

C1 test voltage mode core-core

UOC

4.00 kV

C1 voltage protection level mode core-PE

Up

85.00 V

C1 test voltage mode core-PE

UOC

4.00 kV

B2 voltage protection level mode core-core

Up

70.00 V

B2 test voltage mode core-core

UOC

1.00 kV

B2 voltage protection level mode core-PE

Up

70.00 V

B2 test voltage mode core-PE

UOC

1.00 kV

C2 nominal discharge current (8/20 µs) per core

In

10.00 kA

C2 total discharge current (8/20 µs) cores-PE

ITotal

20.00 kA

C3 nominal discharge current (10/1000 µs) core-PE

ISM

10 A

C3 nominal discharge current (10/1000 µs) core-core

ISM

10 A

C2 voltage protection level mode core-PE at In

Up

95 V

C2 test voltage mode core-PE

UOC

20.00 kV

C2 voltage protection level mode core-core at In

Up

95 V

C2 test voltage mode core-core

UOC

20.00 kV

C3 voltage protection level mode core-PE at 1 kV/µs

Up

70 V

C3 voltage protection level mode core-core at 1 kV/µs

Up

70 V

Response time core-core

ta

1 ns

Response time core-PE

ta

1 ns

Connection (input - output)

terminals-terminals

Cross-section of connected conductors solid (max)

4.00 mm2

Cross-section of connected conductors stranded (max)

4.00 mm2

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 80 °C

Humidity

5 - 95 %

According to standard

EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012

ETIM Class

EC001625

Customs tariff number

85363010

EAN

8595090567295



PDimensions:







Write a review

Note: HTML is not translated!
Captcha

Surge protection for 2-core signalling lines, installation close to protected equipment, 48 V DC, max. 0,5 A

0 reviews / Write a review

* Required fields



Related Product

Combined lightning current arrester, 50 kA

Combined lightning current arrester, 50 kA

Pluggable module, visual fault signalling, module locking.Two-pole high performance lightning curr..

Combined lightning current arrester, 50 kA

Combined lightning current arrester, 50 kA

Pluggable module, visual fault signalling, module locking, remote fault signalling.Combination of ..

Combined lightning current arrester, 50 kA

Combined lightning current arrester, 50 kA

Pluggable module, visual fault signalling, module locking.Combination of one-pole high performance..

Combined lightning current arrester,25 kA

Combined lightning current arrester,25 kA

Pluggable module, visual fault signalling, module locking, remote fault signalling.One-pole high p..