Coupling impedance (R – resistance).
- Coarse and fine surge protection for 2-core signalling lines.
- Installation close to protected equipment.
- For protection of communication interfaces of I<(>&<)>C, electronic security and fire detection systems, etc. (mainly for RS-485 interfaces) against impact of surge voltage.
- Coarse and fine surge protection in differential mode (core – core) and common mode (core – PE).
Specifications:
Parameter name |
Parameter
value |
|
Type of SPD |
D1,C1,C2,C3,B2 |
|
Location of SPD |
ST 2+3 |
|
Mounting |
DIN rail
35 mm |
|
Nominal voltage |
Un |
24 V DC |
Maximum operating voltage |
Uc |
25.00 V
AC |
Maximum operating voltage |
Uc |
36.00 V
DC |
Nominal load current |
IL |
0.500 A |
Treshold frequency core-core |
f |
4.00 MHz |
Serial resistance per core |
R |
1.00 Ω |
D1 total discharge current (10/350 µs) cores-PE |
ITotal |
1.00 kA |
C1 voltage protection level mode core-core |
Up |
65.00 V |
C1 test voltage mode core-core |
UOC |
4.00 kV |
C1 voltage protection level mode core-PE |
Up |
65.00 V |
C1 test voltage mode core-PE |
UOC |
4.00 kV |
B2 voltage protection level mode core-core |
Up |
50.00 V |
B2 test voltage mode core-core |
UOC |
1.00 kV |
B2 voltage protection level mode core-PE |
Up |
50.00 V |
B2 test voltage mode core-PE |
UOC |
1.00 kV |
C2 nominal discharge current (8/20 µs) per core |
In |
10.00 kA |
C2 total discharge current (8/20 µs) cores-PE |
ITotal |
20.00 kA |
C3 nominal discharge current (10/1000 µs) core-PE |
ISM |
10 A |
C3 nominal discharge current (10/1000 µs) core-core |
ISM |
10 A |
C2 voltage protection level mode core-PE at In |
Up |
75 V |
C2 test voltage mode core-PE |
UOC |
20.00 kV |
C2 voltage protection level mode core-core at In |
Up |
75 V |
C2 test voltage mode core-core |
UOC |
20.00 kV |
C3 voltage protection level mode core-PE at 1 kV/µs |
Up |
50 V |
C3 voltage protection level mode core-core at 1 kV/µs |
Up |
50 V |
Response time core-core |
ta |
1 ns |
Response time core-PE |
ta |
1 ns |
Connection (input - output) |
terminals-terminals |
|
Cross-section of connected conductors solid (max) |
4.00 mm2 |
|
Cross-section of connected conductors stranded (max) |
4.00 mm2 |
|
Degree of protection |
IP 20 |
|
Range of ambient temperatures (min/max) |
-40 / 80
°C |
|
Humidity |
5 - 95 % |
|
According to standard |
EN
61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012 |
|
ETIM Class |
EC001625 |
|
Customs tariff number |
85363010 |
|
EAN |
8595090567288 |
Dimensions:
Surge protection for 2-core signalling lines, installation close to protected equipment, 24 V DC, max. 0,5 A.
Related Product
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking.Two-pole high performance lightning curr..
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking, remote fault signalling.Combination of ..
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking.Combination of one-pole high performance..
Combined lightning current arrester,25 kA
Pluggable module, visual fault signalling, module locking, remote fault signalling.One-pole high p..