• Surge protection for 3-core line (combination of signal and supply lines), signal ground separated from protective earth, 24 V DC, pluggable module, floating

Pluggable module, coupling impedance (R – resistance) in part of data, line separated from protective earth via GDT

  • Surge protection of 3-core line comprehend signal transmission and supply
  • Installation close to protected equipment
  • For protection of interfaces of I&C, electronic security and fire detection systems, etc., mainly for measuring circuits and sensors where signal and supply are transmited in one cable, against surge voltage
  • Single common wire for power supply and signal transmission


Specifications:

Parameter name

Parameter value

Cross-section of connected conductors solid (min)

0.14 mm2

Cross-section of connected conductors solid (max)

4.00 mm2

Cross-section of connected conductors stranded (min)

0.14 mm2

Cross-section of connected conductors stranded (max)

2.50 mm2

Fault indication

red indicator

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 70 °C

Humidity

5 - 95 %

According to standard

EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012

ETIM Class

EC001473

Plug module

DMP-024-V/1-J-0

Nominal voltage

Un

24 V AC

Maximum operating voltage

Uc

25.00 V AC

Maximum operating voltage

Uc

36.00 V DC

Nominal load current

IL

16.000 A

Maximum overcurrent protection

16 A gL/gG nebo B 16 A

C2 nominal discharge current (8/20 µs) core-core

In

2.00 kA

Test voltage L+(L-)-PE

4.0 kV

Test voltage M-PE

4.0 kV

voltage protection level L+(L-)-PE

0.75 kV

voltage protection level M-PE

0.75 kV

C2 voltage protection level mode M-PE at In

750.00 V

C2 voltage protection level mode core-PE at In

Up

750 V

Response time L+(L-)-PE

100 ns

Response time M-PE

100 ns

Nominal voltage

Un

24 V DC

Maximum operating voltage

Uc

25.00 V AC

Maximum operating voltage

Uc

36.00 V DC

Nominal load current

IL

1.000 A

Treshold frequency core-core

4.00 MHz

Serial resistance per core

R

0.80 Ω

C2 nominal discharge current (8/20 µs) GND-PE

10.00 kA

C2 nominal discharge current (8/20 µs) core-PE

In

10.00 kA

C2 nominal discharge current (8/20 µs) per core

In

10.00 kA

C3 nominal discharge current (10/1000 µs) GND-PE

10.00 A

C3 nominal discharge current (10/1000 µs) core-PE

10.00 A

C3 voltage protection level mode GND-PE at 1 kV/µs

550.00 V

C3 voltage protection level mode core-GND at 1 kV/µs

46.00 V

Response time core-GND

1 ns

Response time GND-PE

100 ns

Customs tariff number

85363010

EAN

8595090558033


Dimensions:


Write a review

Note: HTML is not translated!
Captcha

Surge protection for 3-core line (combination of signal and supply lines), signal ground separated from protective earth, 24 V DC, pluggable module, floating

0 reviews / Write a review

* Required fields



Related Product

Combined lightning current arrester, 50 kA

Combined lightning current arrester, 50 kA

Pluggable module, visual fault signalling, module locking.Two-pole high performance lightning curr..

Combined lightning current arrester, 50 kA

Combined lightning current arrester, 50 kA

Pluggable module, visual fault signalling, module locking, remote fault signalling.Combination of ..

Combined lightning current arrester, 50 kA

Combined lightning current arrester, 50 kA

Pluggable module, visual fault signalling, module locking.Combination of one-pole high performance..

Combined lightning current arrester,25 kA

Combined lightning current arrester,25 kA

Pluggable module, visual fault signalling, module locking, remote fault signalling.One-pole high p..