Pluggable module, coupling impedance (R – resistance) in part of data, line separated from protective earth via GDT
- Surge protection of 3-core line comprehend signal transmission and supply
- Installation close to protected equipment
- For protection of interfaces of I&C, electronic security and fire detection systems, etc., mainly for measuring circuits and sensors where signal and supply are transmited in one cable, against surge voltage
- Single common wire for power supply and signal transmission
Specifications:
Parameter name |
Parameter value |
|
Cross-section
of connected conductors solid (min) |
0.14 mm2 |
|
Cross-section
of connected conductors solid (max) |
4.00 mm2 |
|
Cross-section
of connected conductors stranded (min) |
0.14 mm2 |
|
Cross-section
of connected conductors stranded (max) |
2.50 mm2 |
|
Fault
indication |
red indicator |
|
Degree
of protection |
IP 20 |
|
Range
of ambient temperatures (min/max) |
-40 / 70 °C |
|
Humidity |
5 - 95 % |
|
According
to standard |
EN 61643-21+A1,A2:2013, IEC
61643-21+A1,A2:2012 |
|
ETIM
Class |
EC001473 |
|
Plug
module |
DMP-024-V/1-J-0 |
|
Nominal
voltage |
Un |
24 V AC |
Maximum
operating voltage |
Uc |
25.00 V AC |
Maximum
operating voltage |
Uc |
36.00 V DC |
Nominal
load current |
IL |
16.000 A |
Maximum
overcurrent protection |
16 A gL/gG nebo B 16 A |
|
C2
nominal discharge current (8/20 µs) core-core |
In |
2.00 kA |
Test
voltage L+(L-)-PE |
4.0 kV |
|
Test
voltage M-PE |
4.0 kV |
|
voltage
protection level L+(L-)-PE |
0.75 kV |
|
voltage
protection level M-PE |
0.75 kV |
|
C2
voltage protection level mode M-PE at In |
750.00 V |
|
C2
voltage protection level mode core-PE at In |
Up |
750 V |
Response
time L+(L-)-PE |
100 ns |
|
Response
time M-PE |
100 ns |
|
Nominal
voltage |
Un |
24 V DC |
Maximum
operating voltage |
Uc |
25.00 V AC |
Maximum
operating voltage |
Uc |
36.00 V DC |
Nominal
load current |
IL |
1.000 A |
Treshold
frequency core-core |
4.00 MHz |
|
Serial
resistance per core |
R |
0.80 Ω |
C2
nominal discharge current (8/20 µs) GND-PE |
10.00 kA |
|
C2
nominal discharge current (8/20 µs) core-PE |
In |
10.00 kA |
C2
nominal discharge current (8/20 µs) per core |
In |
10.00 kA |
C3
nominal discharge current (10/1000 µs) GND-PE |
10.00 A |
|
C3
nominal discharge current (10/1000 µs) core-PE |
10.00 A |
|
C3
voltage protection level mode GND-PE at 1 kV/µs |
550.00 V |
|
C3
voltage protection level mode core-GND at 1 kV/µs |
46.00 V |
|
Response
time core-GND |
1 ns |
|
Response
time GND-PE |
100 ns |
|
Customs
tariff number |
85363010 |
|
EAN |
8595090558033 |
Dimensions:
Surge protection for 3-core line (combination of signal and supply lines), signal ground separated from protective earth, 24 V DC, pluggable module, floating
Related Product
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking.Two-pole high performance lightning curr..
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking, remote fault signalling.Combination of ..
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking.Combination of one-pole high performance..
Combined lightning current arrester,25 kA
Pluggable module, visual fault signalling, module locking, remote fault signalling.One-pole high p..