Pluggable module, visual fault signalling,
middle conductor separated from protective earth via GDT.
- Surge protection for all types of LV electric
and electronic equipments against surge voltage.
- Installation to LV installations, close to
protected equipment.
- For protection of the equipments against impact of induced overvoltages during a lightning strike or switching overvoltages.
Specifications:
Parameter name |
Parameter value |
|
Type
of SPD |
T3, C2 |
|
Location
of SPD |
ST 2 |
|
Mounting |
DIN rail 35 mm |
|
Nominal
voltage |
Un |
48 V AC |
Maximum
operating voltage |
Uc |
60.00 V AC |
Maximum
operating voltage |
Uc |
60.00 V DC |
Nominal
load current |
IL |
16.000 A |
Maximum
overcurrent protection |
16 A gL/gG or B 16 A |
|
C2
nominal discharge current (8/20 µs) per core |
In |
2.00 kA |
Test
voltage L+ - L- |
4.0 kV |
|
Test
voltage L+(L-)-PE |
4.0 kV |
|
Test
voltage M-PE |
4.0 kV |
|
voltage
protection level L+ - L- |
0.37 kV |
|
voltage
protection level L+(L-)-PE |
0.75 kV |
|
voltage
protection level M-PE |
0.75 kV |
|
C2
voltage protection level mode core-PE at In |
750.00 V |
|
C2
voltage protection level mode core-PE at In |
Up |
750 V |
C2
voltage protection level mode core-core at In |
Up |
370 V |
Response
time L+ - L- |
25 ns |
|
Response
time L+(L-)-PE |
100 ns |
|
Response
time M-PE |
100 ns |
|
Connection
(input - output) |
terminals-terminals |
|
Cross-section
of connected conductors solid (min) |
0.14 mm2 |
|
Cross-section
of connected conductors solid (max) |
4.00 mm2 |
|
Cross-section
of connected conductors stranded (min) |
0.14 mm2 |
|
Cross-section
of connected conductors stranded (max) |
2.50 mm2 |
|
Fault
indication |
red indicator |
|
Degree
of protection |
IP 20 |
|
Range
of ambient temperatures (min/max) |
-40 / 70 °C |
|
Humidity |
5 - 95 % |
|
According
to standard |
EN 61643-21+A1,A2:2013, IEC
61643-21+A1,A2:2012, EN 61643-11:2012, IEC 61643-11:2011 |
|
ETIM
Class |
EC000942 |
|
Plug
module |
DP-048-V/1-0 |
|
Customs
tariff number |
85363030 |
|
EAN |
8595090556664 |
Dimensions:
Replacement module: DP-048-V/1-0
Surge protection for small-voltage AC/DC power supply networks, up to 48 V DC, pluggable module
Related Product
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking.Two-pole high performance lightning curr..
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking, remote fault signalling.Combination of ..
Combined lightning current arrester, 50 kA
Pluggable module, visual fault signalling, module locking.Combination of one-pole high performance..
Combined lightning current arrester,25 kA
Pluggable module, visual fault signalling, module locking, remote fault signalling.One-pole high p..