Specifications:


Parameter name

Parameter value

Type of SPD

C2,C3

Location of SPD

ST 2+3

Mounting

DIN rail 35 mm

Maximum operating voltage

Uc

6.00 V AC

Maximum operating voltage

Uc

8.50 V DC

Nominal load current

IL

0.060 A

Serial resistance per core

R

0.27 Ω

C2 nominal discharge current (8/20 µs) SH-PE

In

5.00 kA

C2 nominal discharge current (8/20 µs) core-SH

In

5.00 kA

C2 voltage protection level mode SH-PE at In

Up

350 V

C2 voltage protection level mode core-SH at In

Up

150 V

C3 voltage protection level mode SH-PE at 1 kV/µs

Up

350 V

C3 voltage protection level mode core-SH at 1 kV/µs

Up

35 V

Response time core-SH

ta

1 ns

Response time SH-PE

ta

100 ns

Connection (input - output)

BNC 75

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 80 °C

According to standard

EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012

ETIM Class

EC001625

Customs tariff number

85363010

EAN

8595090533764



Dimensions:








Write a review

Note: HTML is not translated!
Captcha

Surge protection eg. for video systems, CCTV, ect., connectors BNC 75 ohm

0 reviews / Write a review

* Required fields



Related Product

Three-phase surge protection, TN and TT, 63 A

Three-phase surge protection, TN and TT, 63 A

Pluggable module, visual fault signalling, module locking, remote fault signalling.Combination of va..

Surge arrester for three-phase system TN-S, 160 kA (8/20 µs)

Surge arrester for three-phase system TN-S, 160 kA (8/20 µs)

Pluggable module, visual fault signalling, module locking, remote fault signalling.Four-pole varis..

Surge arrester for three-phase system TN-S, 160 kA (8/20 µs)

Surge arrester for three-phase system TN-S, 160 kA (8/20 µs)

Pluggable module, visual fault signalling, module locking.Fur-pole varistor surge arrester.Install..

Varistor surge arrester, TN and IT systems, 690 V AC, 120 kA (8/20)

Varistor surge arrester, TN and IT systems, 690 V AC, 120 kA (8/20)

Pluggable module, visual fault signalling, module locking.Three-pole varistor surge arrester.Insta..