• Surge protection in differencial mode for max. 4-core signalling lines, 24 V DC, up to 1 A

Pluggable module, coupling impedance (R – resistance), shielding (G) separated from protective earth via GDT.

  • Coarse and fine surge protection for max. 4-core signalling lines.
  • Installation close to protected equipment.
  • For protection of communication interfaces of I <(>&<)>C, electronic security and fire detection systems, etc. (mainly for RS-485 interfaces) against impact of surge voltage.
  • Coarse and fine surge protection only in differential mode (core – core).


Specifications:

Parameter name

Parameter value

Type of SPD

C2

Location of SPD

ST 2+3

Mounting

DIN rail 35 mm

Nominal voltage

Un

24 V DC

Maximum operating voltage

Uc

25.00 V AC

Maximum operating voltage

Uc

36.00 V DC

Nominal load current

IL

1.000 A

Treshold frequency core-core

f

6.00 MHz

Serial resistance per core

R

0.80 Ω

C2 nominal discharge current (8/20 µs) GND-PE

In

10.00 kA

C2 nominal discharge current (8/20 µs) per core

In

10.00 kA

C3 voltage protection level mode GND-PE at 1 kV/µs

Up

550.00 V

C3 voltage protection level mode core-core at 1 kV/µs

Up

46 V

Response time core-core

ta

1 ns

Response time GND-PE

ta

100 ns

Connection (input - output)

terminals-terminals

Cross-section of connected conductors solid (min)

0.14 mm2

Cross-section of connected conductors solid (max)

4.00 mm2

Cross-section of connected conductors stranded (min)

0.14 mm2

Cross-section of connected conductors stranded (max)

2.50 mm2

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 70 °C

According to standard

EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012

ETIM Class

EC001625

Customs tariff number

85363010

EAN

8595090562818


Dimensions:



Write a review

Note: HTML is not translated!
Captcha

Surge protection in differencial mode for max. 4-core signalling lines, 24 V DC, up to 1 A

0 reviews / Write a review

* Required fields



Related Product

AC diverter ,for suppression of AC voltage

AC diverter ,for suppression of AC voltage

SPD for Cathodic Corrosion Protection System.Combines an AC current diverter and a SPD in one enclos..

Digital tester for status monitor of SPDs

Digital tester for status monitor of SPDs

Measurement of insulation resistance. It can be used to provide a more accurate imagine of the SPD s..

Automatic VLD class 2 tester

Automatic VLD class 2 tester

Portable automatic tester of VLD class 2.Fully automatic measurement.Measurement of Non-triggering v..

Voltage limiting device, VLD of class 2.2, type VLD-O+F

Voltage limiting device, VLD of class 2.2, type VLD-O+F

Voltage limiting device, VLD of class 2.2, type VLD-O+F, limiting of occurrence non-permissible touc..