Surge
protection for analog telephone line and xDSL.
- Two-stage
surge protection of analog telephone line and xDSL.
- Installation
at boundary LPZ 0 - 1 and higher.
- Connection of metallic pair via screw terminals.
- Working voltage up to 170 V DC.
Specifications:
Parameter name |
Parameter
value |
|
Type of SPD |
D1,C2,C3 |
|
Location of SPD |
ST
1+2+3 |
|
Mounting |
DIN
rail 35 mm |
|
Maximum operating voltage |
Uc |
170.00
V DC |
Serial resistance per core |
R |
10.00
Ω |
Nominal load current |
IL |
0.300
A |
C2 nominal discharge current (8/20
µs) core-core |
In |
5.00
kA |
D1 total discharge current (10/350
µs) cores-PE |
ITotal |
5.00
kA |
C2 voltage protection level mode
core-core (@Uoc/In) |
Up |
600,00
V (10 kV / 5 kA) |
C2 voltage protection level mode
core-PE (@Uoc/In) |
Up |
900,00
V (10 kV / 5 kA) |
C3 voltage protection level mode
core-core (@In - 1 kV/µs) |
Up |
250,00
V (10 A) |
C3 voltage protection level mode
core-PE (@In - 1 kV/µs) |
Up |
550,00
V (10 A) |
Response time core-core |
ta |
1
ns |
Response time core-PE |
ta |
100
ns |
Treshold frequency core-core |
f |
150
MHz (@ −1 dB) |
Insertion loss |
A |
<1
dB (@ 35 MHz) |
Connection (input - output) |
terminals-terminals |
|
Degree of protection |
IP
20 |
|
Range of ambient temperatures
(min/max) |
-40
/ 70 °C |
|
Humidity |
5
- 95 % |
|
According to standard |
EN
61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012 |
|
ETIM Class |
EC000943 |
|
Customs tariff number |
85363010 |
|
EAN |
8595090570844 |
Dimensions:
Two-stage surge protection for analog telephone line and xDSL.
Related Product
AC diverter ,for suppression of AC voltage
SPD for Cathodic Corrosion Protection System.Combines an AC current diverter and a SPD in one enclos..
Digital tester for status monitor of SPDs
Measurement of insulation resistance. It can be used to provide a more accurate imagine of the SPD s..
Automatic VLD class 2 tester
Portable automatic tester of VLD class 2.Fully automatic measurement.Measurement of Non-triggering v..
Voltage limiting device, VLD of class 2.2, type VLD-O+F
Voltage limiting device, VLD of class 2.2, type VLD-O+F, limiting of occurrence non-permissible touc..