• Surge protection,TN and TT systems, 25 A, up to 150 V AC

Visual fault signalling.

  • Universally applicable SPD for all types of LV electric and electronic equipments against surge voltage.
  • Installation to LV installations, close to protected equipment.
  • For protection of the equipments against impact of induced overvoltages during a lightning strike or switching overvoltages.


Specifications:


Parameter name

Parameter value

Type of SPD

T3

Mounting

DIN rail 35 mm

Nominal voltage

Un

120 V AC

Maximum operating voltage

Uc

150.00 V AC

Nominal load current

IL

25.000 A

Type of network

TN

Maximum overcurrent protection

25 A gL/gG or B 25 A

Short-circuit current rating

ISCCR

1.5 kA

Residual current

IPE

0.005 mA

Nominal discharge current (8/20 µs) L-N

In

2.50 kA

Nominal discharge current (8/20 µs) L+N-PE

In

2.50 kA

Nominal discharge current (8/20 µs) N-PE

In

2.50 kA

Test voltage L-N

Uoc

5.0 kV

Test voltage L+N-PE

Uoc

5.0 kV

Test voltage N-PE

Uoc

5.0 kV

Voltage protection level mode L-N

Up

0.63 kV

Voltage protection level mode L-PE

Up

1.10 kV

Voltage protection level mode N-PE

Up

1.10 kV

Response time L-N

ta

25 ns

Response time N-PE

ta

100 ns

TOV 5 s L-N

240 V

TOV characteristic (TOV 5 s)

withstand

Cross-section of connected conductors solid (max)

6.00 mm2

Cross-section of connected conductors stranded (max)

6.00 mm2

Fault indication

red indicator

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 80 °C

Humidity

5 - 95 %

According to standard

EN 61643-11:2012, IEC 61643-11:2011

ETIM Class

EC000942

Customs tariff number

85363030

EAN

8595090560951


Write a review

Note: HTML is not translated!
Captcha

Surge protection,TN and TT systems, 25 A, up to 150 V AC

0 reviews / Write a review

* Required fields



Related Product

AC diverter ,for suppression of AC voltage

AC diverter ,for suppression of AC voltage

SPD for Cathodic Corrosion Protection System.Combines an AC current diverter and a SPD in one enclos..

Digital tester for status monitor of SPDs

Digital tester for status monitor of SPDs

Measurement of insulation resistance. It can be used to provide a more accurate imagine of the SPD s..

Automatic VLD class 2 tester

Automatic VLD class 2 tester

Portable automatic tester of VLD class 2.Fully automatic measurement.Measurement of Non-triggering v..

Voltage limiting device, VLD of class 2.2, type VLD-O+F

Voltage limiting device, VLD of class 2.2, type VLD-O+F

Voltage limiting device, VLD of class 2.2, type VLD-O+F, limiting of occurrence non-permissible touc..