The Server Technology® PRO1 Smart PDU provides local LED input current monitoring, allowing IT personnel to determine safe levels of loading on a per-phase basis while installing equipment into the rack/cabinet. The integral PIPS® technology provides billing-grade accurate measurement of current, voltage, active power, apparent power, power factor, crest factor, and accumulated energy at the input. These power data points, along with temperature and humidity measurements (provided via optional probes), are accessible through the built-in Web and CLI interfaces as well as through SNMP. The PRO1 Smart “Master” PDU can be connected to as many as three (with optional module) PRO1 Smart “Link” PDU to extend the network access to the redundant or secondary power feed without the risks of a daisy chain linking configuration.
Key Features
Network Monitoring
| Hot-Swap Network Card
|
Star Multi-Linking
| Temperature/Humidity Monitoring
|
Auto-Flip Current Display
| Per-Inlet Power Sensing
|
Branch Circuit Protection
| High Retention Locking Outlets
|
High Temperature Rating
| Power Pivot™
|
Flexible Mounting
| Color Identification
|
Cisco EnergyWise¹ Compliant
|
|
INPUTS
Input Voltage (V) | 230 |
Input Plug | IEC 230V/32A 2P+PE 6Hr |
Input Current (A) | 32 |
Input Current Rated (A) | 32 |
Input Power Capacity (kW) | 7.3 |
OUTPUTS
Connector | Rating |
(24) x IEC 60320/C13 | Global Rating: ≤ 10A @230V L-N |
(6) x IEC 60320/C19 | Global Rating: ≤ 16A @230V L-N |
Branch Circuit Protection
- UL498 Compliant 2-pole, 20A trip circuit breakers, two (2) branch, rating: ≤ 16A, 5 kAIC Interrupt Rating
Physical
- Dimensions: 60.0in tall x 1.75in wide x 2.25in deep [1524mm x 45mm x 58mm]
Environmental
- Operating Environment: 32°F to 140°F / 0°C to 60°C | 8%RH to 90%RH non-condensing | 6,500ft/2km elevation
- Storage Environment: -40°F to 185°F / -40°C to 85°C | 8%RH to 90%RH non-condensing | 50,000ft/15km elevation Quiescent / Unloaded Power Draw: < 10W for all configurations
Communications & Security
- 10/100 Mbps Ethernet (RJ-45 connector), RS-232 serial (RJ-45 connector)
- Two (2) temperature/humidity sensor inputs (4P4C), Link port (RJ-12) - {also on Link PDU} Web-browser GUI and command-line interface (CLI): HTTP/HTTPS, TLSv1.2, SSHv2, Telnet, SNMPv2c and v3 (GET, SET, Traps), IPv4 and IPv6, LDAPv3/LDAPS, TACACS+, RADIUS, FTP/SFTP
Certifications
Global:
- TUV T-Mark to EN 60950-1:2006+A11+A1+A12+A2
- EMC to EN55024 (2010) and EN55032 (2012)
- CE Compliant
- RoHS, European Hazardous Materials Directive (Recast) 2011/65/EU
- WEEE Compliant
- LED Current = ± 10% at 0.1 amp (0.3 - 9.9 amps) and 1 amp (> 9.9 amps) resolution
- GUI Current = ± 1% at 0.01 amp resolution (above 0.25 amp)
- Voltage = ± 1% at 0.1 volt resolution (nominal ± 10%)
- Active Power = ± 1% at 1 watt resolution
- Apparent Power = ± 1% at 1 volt-amp resolution
- Power Factor = ± 3% at 0.01 resolution
- Crest Factor = ± 10% at 0.1 resolution
- Energy = ± 1% at 0.1 kilowatt-hour resolution