• DL-1G-RJ45-5V

two-stage protection of Ethernet, instalation at the entrance of th line into the stucture and close to equipment,

at the boundary of LPZ 0 and LPZ 1 or higher, for protection of Ethernet network Cat. 6 against surge over voltage

Technical specifications

Type of SPD

 

D1,C2,C3

Location of SPD 

 

ST 1+2+3

Maximum operating voltage 

Uc

9V DC

Nominal load current 

IL

0,500A

C2 nominal discharge current (8/20 µs) per core `

In

0,15kA

C2 total discharge current (8/20 µs) cores-PE 

ITotal

10,00kA

D1 total discharge current (10/350 µs) cores-PE 

ITotal

2,00kA

C2 voltage protection level mode core-core at In 

Up

50V

C2 voltage protection level mode core-PE at In 

Up

400V

C3 voltage protection level mode core-core at 1 kV/µs 

Up

20V

C3 voltage protection level mode core-PE at 1 kV/µs 

Up

350V

Response time core-core 

ta

1ns

Response time core-PE 

ta

100ns

Insertion attenuation at 250 MHz 

1,50dB

Connection (input - output) 

RJ 45/RJ 45

Degree of protection 

 

IP 20

Range of operating temperatures - min

 

-40 °C

Range of operating temperatures - max 

 

80 °C

ETIM Class 

 

EC000943

According to standard

 

EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012

Write a review

Note: HTML is not translated!
    Bad           Good
Captcha

DL-1G-RJ45-5V

* Required fields


Related Product

Dual Optical Loss Test Set + VisiTester, T27622

Dual Optical Loss Test Set + VisiTester, T27622

A Dual Optical Loss Test Set used to test power, loss, continuity and faults on single mode fiber o..

Manual, hydraulic twin speed crimping tool

Manual, hydraulic twin speed crimping tool

Specificationø mm2KN<-->kg400130488x149 mm4,8..

 Patch Cord CAT6A U/FTP 26AWG 5m LSZH -Grey

Patch Cord CAT6A U/FTP 26AWG 5m LSZH -Grey

Foiled Twisted Pair (FTP) Category 6a (CAT6-Augmented) are constructed of shielded 4-pair copper cab..

25.00AED

outTEG II Double Fan

outTEG II Double Fan

The outdoor cabinet outTEG II Double Fan works exactly as the naturally-ventilated ca..