• CLSA-24

Combination of coarse and fine protection of data and M&C lines. For LSA separating strips.

Technical specifications

Type of SPD

 

C3,C2

Connection (input - output) 

 

LSA disconnection rail

Accessories 

 

grounding rail

Location of SPD 

 

ST 2+3

Maximum operating voltage 

Un

25V AC

Maximum operating voltage 

Uc

36V DC

Nominal load current 

IL

0,500A

C2 nominal discharge current (8/20 µs) per core `

In

500kA

C2 total discharge current (8/20 µs) cores-PE 

ITotal

10,00kA

C2 voltage protection level mode core-PE at In

Up

400V

C3 voltage protection level mode core-core at 1 kV/µs 

Up

48V

C3 voltage protection level mode core-PE at 1 kV/µs 

Up

350V

Response time core-core 

ta

1ns

Response time core-PE 

ta

100ns

Serial resistance per core 

R

1,60Ω

Treshold frequency core-core 

f

4,00MHz

Degree of protection 

 

IP 20

Range of operating temperatures - min

 

-40 °C

Range of operating temperatures - max 

 

70 °C

Mounting 

 

LSA disconnection rail

According to standard

 

EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012

ETIM Class 

 

EC001625

Write a review

Note: HTML is not translated!
Captcha

CLSA-24

0 reviews / Write a review

* Required fields



Related Product

Cable Pulling Grip With One Eye 19 - 25mm L700mm - 2800kgs

Cable Pulling Grip With One Eye 19 - 25mm L700mm - 2800kgs

Hand woven galvanized steel wire mesh with a Talurit coupling, and one reinforced pulling ..

AED 218.00

Plastic cable roller

Plastic cable roller

Specificationkgø 142 - ø 60 ↔ 172 mm280 x 220 x 230 mm1,7..

Cable External FO 6C 62.5/125 L/T HDPE -Black

Cable External FO 6C 62.5/125 L/T HDPE -Black

ACOLAN®  Loose Tube6 fibers – Outdoor – HDPEDielectric – Dry water tightness62.5/125 OM1Th..

AED 13.35

outTEG II Double Active

outTEG II Double Active

The outdoor cabinet outTEG II Double Active provides better thermal regulation of installe..