Combination of coarse and fine protection of telecommunication equipment including ADSL. For protection of M&C and data lines and ISDN lines. For LSA separating strips .
Technical specifications
Type of SPD | C3,C2 | |
Connection (input - output) | LSA disconnection rail | |
Accessories | grounding rail | |
Location of SPD | ST 2+3 | |
Maximum operating voltage | Un | 120V AC |
Maximum operating voltage | Uc | 170V DC |
Nominal load current | IL | 0,500A |
C2 nominal discharge current (8/20 µs) per core ` | In | 500kA |
C2 total discharge current (8/20 µs) cores-PE | ITotal | 10,00kA |
C2 voltage protection level mode core-PE at In | Up | 280V |
C2 voltage protection level mode core-core at In | 350V | |
C3 voltage protection level mode core-core at 1 kV/µs | Up | 230V |
C3 voltage protection level mode core-PE at 1 kV/µs | Up | 400V |
Response time core-core | ta | 1ns |
Response time core-PE | ta | 100ns |
Serial resistance per core | R | 1,60Ω |
Treshold frequency core-core | f | 65,00MHz |
Degree of protection | IP 20 | |
Range of operating temperatures - min | -40 °C | |
Range of operating temperatures - max | 70 °C | |
Mounting | LSA disconnection rail | |
According to standard | N 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012 | |
ETIM Class | EC001625 |
CLSA-DSL
Related Product
Adjustable boom for cable guiding device
Specification<-->kg140-240cm14..
High resistance polyester rope
SpecificationPart Numberø<-->kgX300010003mm2,51'000m5,1X500010005mm5,01'000m9,2..
Inline Power Modules
This industrial family of Sentry Inline Power Modules (IPMs) has been designed to provide Remote Pow..
AED 135.00
Distribution Box Ext 50pr DBF With BMF Empty LSA
housing with hinged cover (opening approx. 110°)space for owner´s label on the cover approx. 24 mm x..
AED 171.04