RJ12 connectors
Type of SPD | C2,C3 | |
Location of SPD | ST 2+3 | |
Maximum operating voltage | Uc | 114 V AC |
Maximum operating voltage | Uc | 162 V AC |
Nominal load current | IL | 0,060 A |
C2 nominal discharge current (8/20 µs) core-core | In | 2,50Ka |
C2 voltage protection level mode core-core at In | Up | 260 V |
C2 voltage protection level mode core-PE at In | Up | 300 V |
C3 voltage protection level mode core-core at 1 kV/µs | Up | 240 V |
C3 voltage protection level mode core-PE at 1 kV/µs | Up | 400 V |
Response time core-core | ta | 1 ns |
Response time COM-PE | ta | 100 ns |
Serial resistance per core | R | 6,80Ω |
Treshold frequency core-core | f | 14,00MHz |
Connection (input - output) |
| RJ 45/RJ 45 |
Degree of protection |
| IP 20 |
Range of operating temperatures - min |
| -40°C |
Range of operating temperatures - max |
| 80°C |
Mounting |
| DIN rail 35 mm |
According to standard |
| EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012 |
ETIM Class |
| EC001625 |