Replaceable varistor module, visual fault signaling.
SPD type | T2 | |
Rated voltage | Un | 230 IN AC |
Maximum continuous operating voltage | Uc | 275 IN AC / 350 IN DC |
Rated discharge current (8/20 microseconds) | In | 20.00kA |
The maximum discharge current (8/20 microseconds) | Imax | 40.00kA |
Voltage protection level at 5 kA | Up | 0.90 kV |
Voltage protection level | Up | 1.35 kV |
Rated short circuit current | I SCCR | 50.0kA |
maximum overcurrent | 160 A gL / gG | |
response time | t and | 25 ns |
TOV 5 LN | 355 IN | |
TOV characteristic (TOV 5s) | withstand | |
TOV LN 120 min | 440 IN | |
TOV characteristic (120 min) | perturbation | |
Output wires solid (min) | 1.00mm 2 | |
Output wires solid (max) | 35.00mm 2 | |
Output wires stranded (min) | 1.00mm 2 | |
Output wires stranded (max) | 25.00mm 2 | |
Signalling faults | red indication field | |
Ingress protection | IP 20 | |
Operating temperature range - min | -40C | |
Operating temperature range - max | 80C | |
Construction | DIN rail 35 mm | |
Meets | EN 61643-11 ed.2 | |
replacement module | SLP-275 V / 0 | |
class ETIM | EC000941 |
Surge Arrester Varistor SPD Type O.V Max 350 VDC
Related Product
Jensen Tools JTK-87B Kit in Backpack Case, black
Tool pallets fold out for easy access. Clear parts pocket provides storage for small tools or test l..
N-Straight Plug G 50 Ohms TA G1 (RG-58C/U); G5 (RG-223/U)
The N series is a very popular coax connector. It is a medium sized, precision, weatherproof connect..
Elicon Worksurface W2000 D800
Working level designed as sliding section for convenient access to the horizontal cable ductThe work..
Simple Test Kit SM TK056
A simple fiber testing kit, excellent for low to modest test volume on single mode systems. An opti..