Combination of coarse and fine protection of telecommunication equipment including ADSL. For protection of M&C and data lines and ISDN lines. For LSA separating strips .
Technical specifications
Type of SPD | C3,C2 | |
Connection (input - output) | LSA disconnection rail | |
Accessories | grounding rail | |
Location of SPD | ST 2+3 | |
Maximum operating voltage | Un | 120V AC |
Maximum operating voltage | Uc | 170V DC |
Nominal load current | IL | 0,500A |
C2 nominal discharge current (8/20 µs) per core ` | In | 500kA |
C2 total discharge current (8/20 µs) cores-PE | ITotal | 10,00kA |
C2 voltage protection level mode core-PE at In | Up | 280V |
C2 voltage protection level mode core-core at In | 350V | |
C3 voltage protection level mode core-core at 1 kV/µs | Up | 230V |
C3 voltage protection level mode core-PE at 1 kV/µs | Up | 400V |
Response time core-core | ta | 1ns |
Response time core-PE | ta | 100ns |
Serial resistance per core | R | 1,60Ω |
Treshold frequency core-core | f | 65,00MHz |
Degree of protection | IP 20 | |
Range of operating temperatures - min | -40 °C | |
Range of operating temperatures - max | 70 °C | |
Mounting | LSA disconnection rail | |
According to standard | N 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012 | |
ETIM Class | EC001625 |
CLSA-DSL
Related Product
Galvanized steel ropes with round section, 7 x 19
SpecificationPart NumberØ mm7 x 19(daN)(Kg/m) StandardJ5040000047 x 191.0080,060500 - 1000J5050..
Manual, hydraulic twin speed crimping tool
Specificationø mm2KN<-->kg18580485x141 mm3,5..
BNC Terminator 50 Ohms Insulated 0.5W 100Mhz>=20db
The BNC series is the most commonly used coax connector. With its bayonet coupling mechanism this co..
AED 10.32
Surge Arrester Varistor SPD Type O.V Max 350 VDC
Replaceable varistor module, visual fault signaling.varistor surge arrester, designed to be installe..