• DL-ISDN RJ45

Connectors RJ45

Combination of coarse and fine protection of one pair of ISDN line of telecommunication equipment. Installation
at the boundary of LPZ 1 and LPZ 2 zones and higher.

Parameters

Type of SPD

 

C2,C3

Location of SPD 

 

ST 2+3

Maximum operating voltage

Uc

86 V AC

Maximum operating voltage

Uc

121 V AC

Nominal load current

IL

0,060 A

C2 nominal discharge current (8/20 µs) core-core 

In

2,50Ka

C2 voltage protection level mode core-core at In 

Up

270 V

C2 voltage protection level mode core-PE at In

Up

300 V

C3 voltage protection level mode core-core at 1 kV/µs 

Up

180 V

C3 voltage protection level mode core-PE at 1 kV/µs 

Up

400 V

Response time core-core 

ta

1 ns

Response time COM-PE

ta

100 ns

Serial resistance per core 

R

6,80Ω

Treshold frequency core-core

f

80,00MHz

Connection (input - output) 

 

RJ 45/RJ 45

Degree of protection

 

IP 20

Range of operating temperatures - min 

 

-40°C

Range of operating temperatures - max 

 

80°C

Mounting 

 

DIN rail 35 mm

According to standard

 

EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012

ETIM Class

 

EC001625

Write a review

Note: HTML is not translated!
Captcha

DL-ISDN RJ45

0 reviews / Write a review

* Required fields



Related Product

Bellmouth Galvanised 76mm

Bellmouth Galvanised 76mm

pecificationkg76mm4,5..

AED 891.00

Toolkit Open HVAC Technician's

Toolkit Open HVAC Technician's

The JTK-1005C Tool Kit is designed with a heavy duty, open mouth tool bag that measures 19" x 9-1/4"..

Jensen Tools JTK-87RTF Kit without Test Equipment

Jensen Tools JTK-87RTF Kit without Test Equipment

SpecificationsDimensions (ID) (L x W x D):17-3/4 x 14-1/2 x 8"Case Style:Rota-Tough™Case Style No.:6..

Adapters and Cables

Adapters and Cables

Adapters and Cables used to complete your PDU installation. Cables and AdaptersDescriptionPart ..

AED 55.00