• CLSA-TLF

Combination of coarse and fine protection of telecommunication equipment including ADSL. For protection of M&C and data lines and ISDN lines. For LSA separating strips .

Technical specifications

Type of SPD

 

C3,C2

Connection (input - output) 

 

LSA disconnection rail

Accessories 

 

grounding rail

Location of SPD 

 

ST 2+3

Maximum operating voltage 

Un

120V AC

Maximum operating voltage 

Uc

170V DC

Nominal load current 

IL

0,500A

C2 nominal discharge current (8/20 µs) per core `

In

500kA

C2 total discharge current (8/20 µs) cores-PE 

ITotal

10,00kA

C2 voltage protection level mode core-PE at In

Up

280V

C2 voltage protection level mode core-core at In 

 

310V

C3 voltage protection level mode core-core at 1 kV/µs 

Up

400V

C3 voltage protection level mode core-PE at 1 kV/µs 

Up

350V

Response time core-core 

ta

1ns

Response time core-PE 

ta

100ns

Serial resistance per core 

R

1,60Ω

Treshold frequency core-core 

f

14,00MHz

Degree of protection 

 

IP 20

Range of operating temperatures - min

 

-40 °C

Range of operating temperatures - max 

 

70 °C

Mounting 

 

LSA disconnection rail

According to standard

 

N 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012

ETIM Class 

 

EC001625

Write a review

Note: HTML is not translated!
Captcha

CLSA-TLF

0 reviews / Write a review

* Required fields



Related Product

outTEG I Single

outTEG I Single

 outdoor single-walled cabinet provides basic protection of installed equipment against al..

Steel duct brush with wire kernal

Steel duct brush with wire kernal

Specificationø:<-->kg80m330mm1,0..

SMA Straight Plug Crimp - RG-58C/U

SMA Straight Plug Crimp - RG-58C/U

The SMA series is a very popular coax connector with threaded coupling, and can be used up to freque..

Fan Assembly 2Way With Thermo - Smaract

Fan Assembly 2Way With Thermo - Smaract

Easy add-on on the rear panelWith two axial fansWith thermostatSingle fan technical dataType 1:Max. ..