Coupling impedance (resistance), screw terminals.
- Coarse and fine surge protection of 2-core
high-speed signalling lines.
- Installation close to protected equipment.
- For protection of communication interfaces,
mainly the RS-485 lines, of I&C, electronic security and fire detection
systems, etc. against impact of surge voltage.
- Coarse and fine surge protection in differential mode (core – core) and coarse surge protection in common mode (core – PE).
Specifications:
Parameter name |
Parameter value |
|
Type
of SPD |
C2,C3 |
|
Location
of SPD |
ST 2+3 |
|
Mounting |
DIN rail 35 mm |
|
Nominal
voltage |
Un |
6 V DC |
Maximum
operating voltage |
Uc |
6.00 V AC |
Maximum
operating voltage |
Uc |
8.50 V DC |
Nominal
load current |
IL |
0.500 A |
Treshold
frequency core-core |
f |
70.00 MHz |
Serial
resistance per core |
R |
1.60 Ω |
D1
impulse discharge current (10/350 µs) per core |
Iimp |
0.50 kA |
D1
total discharge current (10/350 µs) cores-PE |
ITotal |
1.00 kA |
C2
nominal discharge current (8/20 µs) per core |
In |
5.00 kA |
C2
total discharge current (8/20 µs) cores-PE |
ITotal |
10.00 kA |
C2
voltage protection level mode core-PE at In |
Up |
350 V |
C2
voltage protection level mode core-core at In |
Up |
26 V |
C3
voltage protection level mode core-PE at 1 kV/µs |
Up |
500 V |
C3
voltage protection level mode core-core at 1 kV/µs |
Up |
14 V |
Response
time core-core |
ta |
1 ns |
Response
time core-PE |
ta |
1 ns |
Connection
(input - output) |
terminals-terminals |
|
Cross-section
of connected conductors solid (min) |
0.14 mm2 |
|
Cross-section
of connected conductors solid (max) |
4.00 mm2 |
|
Cross-section
of connected conductors stranded (min) |
0.14 mm2 |
|
Cross-section
of connected conductors stranded (max) |
2.50 mm2 |
|
Degree
of protection |
IP 20 |
|
Range
of ambient temperatures (min/max) |
-40 / 70 °C |
|
According
to standard |
EN 61643-21+A1,A2:2013, IEC
61643-21+A1,A2:2012 |
|
ETIM
Class |
EC001625 |
|
Customs
tariff number |
85363010 |
|
EAN |
8595090551386 |
Dimensions:
Surge protection for 2-core high-speed floating signalling lines, 6 V DC, max. 0.5 A
Related Product
Universal disconnection rail LSA
Universal disconnection rail LSA 2/10. Universal disconnection rail LSA 2/10.Specifications:Param..
Mounting frame – 1 position for CLSA
Mounting frame – 1 position. Mounting frame – 1 position for CLSA.Specifications: ..
Empty module cover
SPD - for data, signalling and telecommunications lines / ICT / Ethernet and PoE - for 19" RACKprote..
Comb grounding rail for CLSA.
Comb grounding rail for CLSA.Specifications: Parameter name Para..