• CLSA-ISDN

Combination of coarse and fine protection of telecommunication equipment including ADSL. For protection of M&C and data lines and ISDN lines. For LSA separating strips .

Technical specifications

Type of SPD

 

C3,C2

Connection (input - output) 

 

LSA disconnection rail

Accessories 

 

grounding rail

Location of SPD 

 

ST 2+3

Maximum operating voltage 

Un

85V AC

Maximum operating voltage 

Uc

120VDC

Nominal load current 

IL

0,500A

C2 nominal discharge current (8/20 µs) per core `

In

500kA

C2 total discharge current (8/20 µs) cores-PE 

ITotal

10,00kA

C2 voltage protection level mode core-PE at In

Up

400V

C2 voltage protection level mode core-core at In 

 

220V

C3 voltage protection level mode core-core at 1 kV/µs 

Up

170V

C3 voltage protection level mode core-PE at 1 kV/µs 

Up

350V

Response time core-core 

ta

1ns

Response time core-PE 

ta

100ns

Serial resistance per core 

R

1,60Ω

Treshold frequency core-core 

f

16,00MHz

Degree of protection 

 

IP 20

Range of operating temperatures - min

 

-40 °C

Range of operating temperatures - max 

 

70 °C

Mounting 

 

LSA disconnection rail

According to standard

 

N 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012

ETIM Class 

 

EC001625

Write a review

Note: HTML is not translated!
Captcha

CLSA-ISDN

0 reviews / Write a review

* Required fields



Related Product

Lightning current arrester for two 2-core signalling lines, max. 180 V

Lightning current arrester for two 2-core signalling lines, max. 180 V

Pluggable module, line separated from protective earth via GDT. Lightning current arrester of ..

Lightning current arrester for two 2-core  signalling lines,max. 70 V

Lightning current arrester for two 2-core signalling lines,max. 70 V

Pluggable module, line separated from protective earth via GDT.Lightning current arrester of two 2/..

Lightning current arrester for two 2-core  signalling lines, max. 180 V.

Lightning current arrester for two 2-core signalling lines, max. 180 V.

Pluggable module.Lightning current arrester of two 2-core signalling lines.Installation at the bound..

Lightning current arrester for two 2-core signalling lines, max. 70 V.

Lightning current arrester for two 2-core signalling lines, max. 70 V.

Pluggable moduleLightning current arrester of two 2-core signalling lines.Installation at the bounda..