Replaceable varistor module, visual fault signaling.
SPD type | T2 | |
Rated voltage | Un | 230 IN AC |
Maximum continuous operating voltage | Uc | 275 IN AC / 350 IN DC |
Rated discharge current (8/20 microseconds) | In | 20.00kA |
The maximum discharge current (8/20 microseconds) | Imax | 40.00kA |
Voltage protection level at 5 kA | Up | 0.90 kV |
Voltage protection level | Up | 1.35 kV |
Rated short circuit current | I SCCR | 50.0kA |
maximum overcurrent | 160 A gL / gG | |
response time | t and | 25 ns |
TOV 5 LN | 355 IN | |
TOV characteristic (TOV 5s) | withstand | |
TOV LN 120 min | 440 IN | |
TOV characteristic (120 min) | perturbation | |
Output wires solid (min) | 1.00mm 2 | |
Output wires solid (max) | 35.00mm 2 | |
Output wires stranded (min) | 1.00mm 2 | |
Output wires stranded (max) | 25.00mm 2 | |
Signalling faults | red indication field | |
Ingress protection | IP 20 | |
Operating temperature range - min | -40C | |
Operating temperature range - max | 80C | |
Construction | DIN rail 35 mm | |
Meets | EN 61643-11 ed.2 | |
replacement module | SLP-275 V / 0 | |
class ETIM | EC000941 |
Surge Arrester Varistor SPD Type O.V Max 350 VDC
Related Product
Cab Tecoras Ext 27U H1440 W770 D900 W/HEX150 Heat Exchanger
Tecoras Outdoor Cabinet 27U H1440 W770 D900 with HEX150 Heat Exchanger Scope of supply:· &..
PDU 10Way Vertical Angled Left UK 13A IEC C14 Plug - 3m
XAL - Vertical Rack Mount Angled Left16 Amps total loadSupplied with 3mtrs flex to 13A UK fused plug..
Kevlar cable pulling grip with two reinforced pulling eyelets
SpecificationCablePart NumberLengthBreak streghtNo point endsWireNo of wiresmm mmkg&n..
Galvanised cable suspension roller
Teflon duct mandrelSpecificationø:<-->kg117mm330mm5,7..