Fine protection for max. 24 ports of Ethernet Cat. 5. Only a shielded version is supplied. Installation at the
boundary of LPZ 2 and LPZ 3 zones, directly in front of the device.
Technical specifications
Type of SPD | C2,C3 | |
Location of SPD | ST 3 | |
Maximum operating voltage | Uc | 6V DC and 8V DC |
Nominal load current | IL | 0,100A |
C2 nominal discharge current (8/20 µs) per core | In | 0,20kA |
C2 total discharge current (8/20 µs) cores-PE | ITotal | 1,60kA |
C2 voltage protection level mode core-core at In | Up | 40V |
C2 voltage protection level mode core-PE at In | Up | 350V |
C3 voltage protection level mode core-core at 1 kV/µs | Up | 65V |
C3 voltage protection level mode core-PE at 1 kV/µs | Up | 350V |
Response time core-core | ta | 1ns |
Response time core-core | ta | 100ns |
Insertion attenuation at 250 MHz | 1,50dB | |
Connection (input - output) | RJ 45/RJ 45 | |
Degree of protection | IP 20 | |
Range of operating temperatures - min | -40 °C | |
Range of operating temperatures - max | 60 °C | |
According to standard | EN 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012 | |
ETIM Class | EC000943 |
DL-Cat. 5e 8 RACK PANEL
Related Product
Air plug
Air Plug - Piston with air tight sealsSpecificationPart Numberø:JZ-TP940091-96mm..
Mountpost 18U Smaract Aluminium (2/Set)
Material / Finish19” Extrusions: extruded aluminium, polished Mounting bracket: sheet steel, zinc-pa..
Jensen Tools JTK-23BLK Multi-Fastener Tool Kit in Black Cordura Case
SpecificationsDimensions (ID) (L x W x D)13-1/2" x 10" x 2-1/2"Case StyleSingle Black CprduraCase St..
Cable Routing Set
For cable routing on, for example, the T-slots of the Knürr extrusionsSupply schedule1 spiral cableM..