• CLSA-TLF

Combination of coarse and fine protection of telecommunication equipment including ADSL. For protection of M&C and data lines and ISDN lines. For LSA separating strips .

Technical specifications

Type of SPD

 

C3,C2

Connection (input - output) 

 

LSA disconnection rail

Accessories 

 

grounding rail

Location of SPD 

 

ST 2+3

Maximum operating voltage 

Un

120V AC

Maximum operating voltage 

Uc

170V DC

Nominal load current 

IL

0,500A

C2 nominal discharge current (8/20 µs) per core `

In

500kA

C2 total discharge current (8/20 µs) cores-PE 

ITotal

10,00kA

C2 voltage protection level mode core-PE at In

Up

280V

C2 voltage protection level mode core-core at In 

 

310V

C3 voltage protection level mode core-core at 1 kV/µs 

Up

400V

C3 voltage protection level mode core-PE at 1 kV/µs 

Up

350V

Response time core-core 

ta

1ns

Response time core-PE 

ta

100ns

Serial resistance per core 

R

1,60Ω

Treshold frequency core-core 

f

14,00MHz

Degree of protection 

 

IP 20

Range of operating temperatures - min

 

-40 °C

Range of operating temperatures - max 

 

70 °C

Mounting 

 

LSA disconnection rail

According to standard

 

N 61643-21+A1,A2:2013, EN IEC 61643-21+A1,A2:2012

ETIM Class 

 

EC001625

Write a review

Note: HTML is not translated!
Captcha

CLSA-TLF

0 reviews / Write a review

* Required fields



Related Product

Cable External FO 6C 62.5/125 OM1 Glass ARM Black

Cable External FO 6C 62.5/125 OM1 Glass ARM Black

1. Optical fibre : Multimode (FOTAG color code)2. Tube : Thermoplastic material3. Tube waterproofing..

AED 5.17

Cable Manager 2U W/ Plastic Ducts H80 D60 - RAL9005

Cable Manager 2U W/ Plastic Ducts H80 D60 - RAL9005

 Wire Management Panels with Plastic DuctsThese wire managers are installed to the 19" extrusio..

AED 105.00

Cable Firekab 2C 1.5sqmm NGF FE 180 PH30- Roll Of 500Mtr

Cable Firekab 2C 1.5sqmm NGF FE 180 PH30- Roll Of 500Mtr

ConstructionConductorSolid bare copper (IEC / EN 228, BS 6360, VDE 0295, HD 383)InsulationFire resis..

AED 4.00

VOLTASPEED

VOLTASPEED

Hydraulic pushing-pulling rods caterpillar VOLTASPEED type, fit for ø 9 - 11 - 15 mm glass fibre rod..