The VT336 / Industial Monitoring Unit can be used for remote environmental monitoring in industrial settings:
- Monitoring:
Measures temperature, humidity, voltage, access, smoke, dust, vibration,
access, leakage, movement, airflow.
- I/O
Controller: 4 analog Plug and Play inputs, CAN input, 10 dry contacts IN
and 5 OUT, 2 relays 12V, SD, USB.
- Scalability:
Supports up to 1000 elements, including sensors, virtual sensors, logic,
notifications.
- Built-in
Web Interface: 100Mbit/s, IPv4, IPv6 by demand.
- Extensions:
4G modem, Modbus.
- Notifications:
Telegram, mail; VPN, SMS and voice call in case of 4G modem built-IN.
- Processor:
720Mhz dual-core Cortex-A7, 128Mbit RAM.
Specification:
- Device type:Environmental monitoring unit
- Network Interface:100Mbit/s, IPv4, IPv6 by demand.
- Analog ports:4 Plug and Play
- Response time:1 sec
- CAN:1
- Max. distance from the unit:Analog Plug and Play sensors:
50-150m, CAN - 225m
- Maximum units in a CAN bus:31, depends on CAN device type
- Relays with output 12V:2
- Dry contacts IN:10
- Dry contacts OUT:5
- Mounting:DIN
- Extensions:SD, USB-C
- Expansions:4G, RS485
- Status Indicators:Red (Error), Green Led, Yellow, Orange
(Relais)
- Processor:Dual core ARM, 720 Mhz, 128 MB
- Power inputs:12V, 24V, 48V DC
- Operating temperature:-10° C to +80° C
- Origin of goods:Made in EU
- HS Code:8537 10 910
Industrial Monitoring Unit VT336T.
Related Product
Sensor Extension Unit.
The VT408 expansion module increases the number of analog sensors that can be connected t..
Mon Unit W/ CAN,Ether Prt,SD,USB,4Anlg,4Dig,2 12V -W/UK Plu.
The VT335 / IT Room Monitoring Unit can be used for remote environmental monitoring in sm..
Smoke Sensor Vutlan.
The VT560 Smoke Detector is designed to monitor the presence of smoke and fire indoors.&n..
Access Sensor.
The VT530 Access Sensor is essential for access control and is designed to monitor the st..