Pluggable module, visual fault signalling, remote fault signalling.
- Four-pole varistor surge arrester.
 - Installation to LV installations, especially to sub-distribution boards in TN-S systems.
 - For protection of the installations and equipments against impact of induced overvoltages during a lightning strike or switching overvoltages.
 
Specifications:
| 
    Parameter name  | 
   
    Parameter
   value  | 
  |
| 
   Type of SPD  | 
  
   T2  | 
 |
| 
   Mounting  | 
  
   DIN
  rail 35 mm  | 
 |
| 
   Nominal voltage  | 
  
   Un  | 
  
   120
  V AC  | 
 
| 
   Maximum operating voltage  | 
  
   Uc  | 
  
   150.00
  V AC  | 
 
| 
   Maximum operating voltage  | 
  
   Uc  | 
  
   200.00
  V DC  | 
 
| 
   Type of network  | 
  
   TN-S  | 
 |
| 
   Maximum overcurrent protection  | 
  
   160
  A gL/gG  | 
 |
| 
   Short-circuit current rating  | 
  
   ISCCR  | 
  
   50.0
  kA  | 
 
| 
   Residual current  | 
  
   IPE  | 
  
   0.350
  mA  | 
 
| 
   Nominal discharge current (8/20 µs)  | 
  
   In  | 
  
   15.00
  kA  | 
 
| 
   Maximum discharge current (8/20 µs)  | 
  
   Imax  | 
  
   40.00
  kA  | 
 
| 
   Voltage protection level  | 
  
   Up  | 
  
   0.74
  kV  | 
 
| 
   Voltage protection level at 5 kA  | 
  
   Up  | 
  
   0.60
  kV  | 
 
| 
   Response time  | 
  
   ta  | 
  
   25
  ns  | 
 
| 
   TOV 5 s L-N  | 
  
   175
  V  | 
 |
| 
   TOV characteristic (TOV 5 s)  | 
  
   withstand  | 
 |
| 
   Cross-section of connected
  conductors solid (min)  | 
  
   4.00
  mm2  | 
 |
| 
   Cross-section of connected
  conductors solid (max)  | 
  
   35.00
  mm2  | 
 |
| 
   Cross-section of connected
  conductors stranded (min)  | 
  
   4.00
  mm2  | 
 |
| 
   Cross-section of connected
  conductors stranded (max)  | 
  
   25.00
  mm2  | 
 |
| 
   Cross-section of remote indication
  conductors solid (max)  | 
  
   1.5
  mm2  | 
 |
| 
   Cross-section of remote indication
  conductors stranded (max)  | 
  
   1.5
  mm2  | 
 |
| 
   Fault indication  | 
  
   red
  indication field  | 
 |
| 
   Remote indication  | 
  
   potential-free
  change-over contact  | 
 |
| 
   Remote indication contacts  | 
  
   250V/0,5A
  AC,250V/0,1A DC  | 
 |
| 
   Degree of protection  | 
  
   IP
  20  | 
 |
| 
   Range of ambient temperatures
  (min/max)  | 
  
   -40
  / 80 °C  | 
 |
| 
   Humidity  | 
  
   5
  - 95 %  | 
 |
| 
   According to standard  | 
  
   EN
  61643-11:2012, IEC 61643-11:2011  | 
 |
| 
   ETIM Class  | 
  
   EC000941  | 
 |
| 
   Plug module  | 
  
   SLP-150
  V/0  | 
 |
| 
   Customs tariff number  | 
  
   85363030  | 
 |
| 
   EAN  | 
  
   8595090574507  | 
 
Dimensions:
Surge arrester , TN-s (120/208 V AC), 160 kA (8/20 µs)
Related Product
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications: Parameter name ..
Replacement module for SLP-PV500 V/U.
Replacement module for SLP-PV1000 V/Y (S).Specifications: Parameter name ..