Pluggable module, visual fault signalling, module locking, remote fault signalling.
- Varistor surge arrester in 'Y' connection.
- For protection of PV systems where the separating spark-over distance is kept or without LPS.
- Maximum continuous operating voltage for PV application: UCPV ≥ 1.2x UOC STC.
Specifications:
Parameter name |
Parameter
value |
|
Type of SPD |
PV
T2 |
|
Mounting |
DIN
rail 35 mm |
|
Maximum operating voltage mode +/PE,
-/PE |
UCPV |
1
500.00 V DC |
Short-circuit current rating |
ISCPV |
10
000 A DC |
Residual current mode +/PE, -/PE |
IPE |
0.250
mA AC |
Residual current mode +/PE, -/PE |
IPE |
0.005
mA DC |
Total discharge current (8/20 µs) |
ITotal(8/20) |
40.00
kA |
Nominal discharge current (8/20 µs) |
In |
15.00
kA |
Maximum discharge current (8/20 µs) |
Imax |
40.00
kA |
Voltage protection level mode +/- |
Up |
6.40
kV |
Voltage protection level mode +/PE,
-/PE |
Up |
6.40
kV |
Response time |
ta |
25
ns |
Cross-section of connected
conductors solid (min) |
1.00
mm2 |
|
Cross-section of connected
conductors solid (max) |
35.00
mm2 |
|
Cross-section of connected
conductors stranded (min) |
1.00
mm2 |
|
Cross-section of connected
conductors stranded (max) |
25.00
mm2 |
|
Cross-section of remote indication
conductors solid (max) |
1.5
mm2 |
|
Cross-section of remote indication
conductors stranded (max) |
1.5
mm2 |
|
Fault indication |
red
indication field |
|
Remote indication |
potential-free
change-over contact |
|
Remote indication contacts |
250V/0,5A
AC,250V/0,1A DC |
|
Degree of protection |
IP
20 |
|
Range of ambient temperatures
(min/max) |
-40
/ 80 °C |
|
According to standard |
EN
61643-31, IEC 61643-31 |
|
ETIM Class |
EC000941 |
|
Customs tariff number |
85354000 |
|
EAN |
8595090543053 |
Dimensions:
Surge arrester for PV systems (both poles), up to 1500 V DC
Related Product
AC diverter ,for suppression of AC voltage
SPD for Cathodic Corrosion Protection System.Combines an AC current diverter and a SPD in one enclos..
Digital tester for status monitor of SPDs
Measurement of insulation resistance. It can be used to provide a more accurate imagine of the SPD s..
Automatic VLD class 2 tester
Portable automatic tester of VLD class 2.Fully automatic measurement.Measurement of Non-triggering v..
Voltage limiting device, VLD of class 2.2, type VLD-O+F
Voltage limiting device, VLD of class 2.2, type VLD-O+F, limiting of occurrence non-permissible touc..