Spark gap for N-PE, pluggable module, module locking.
- For connection Type 1 SPD
in 3+1 mode.
- Installation at the
boundary of zones LPZ 0 and LPZ 1 or higher, mainly to main distribution boards.
- For protection against impact of direct or indirect lightning strikes.
Specifications:
|
Parameter name |
Parameter value |
|
|
Type of SPD |
T1 |
|
|
Mounting |
DIN rail 35 mm |
|
|
Maximum operating voltage |
Uc |
255.00 V AC |
|
Nominal load current for "V" connection |
IL |
125 A |
|
Type of network |
TT |
|
|
Nominal discharge current (8/20 µs) |
In |
100.00 kA |
|
Maximum discharge current (8/20 µs) |
Imax |
100.00 kA |
|
Voltage protection level |
Up |
1.50 kV |
|
Ability to independently switch off the following current |
Ifi |
0.1 kA |
|
Response time |
ta |
100 ns |
|
TOV 200 ms N-PE |
1 200 V |
|
|
TOV characteristic (TOV 200 ms) |
withstand |
|
|
Cross-section of connected conductors solid (min) |
2.50 mm2 |
|
|
Cross-section of connected conductors solid (max) |
50.00 mm2 |
|
|
Cross-section of connected conductors stranded (min) |
2.50 mm2 |
|
|
Cross-section of connected conductors stranded (max) |
35.00 mm2 |
|
|
Cross-section of remote indication conductors solid (max) |
1.5 mm2 |
|
|
Cross-section of remote indication conductors stranded (max) |
1.5 mm2 |
|
|
Fault indication |
remote signalling of
N-PE module shows the presence of the replaceable module |
|
|
Remote indication |
potential-free
change-over contact |
|
|
Remote indication contacts |
250V/0,5A AC,250V/0,1A
DC |
|
|
Degree of protection |
IP 20 |
|
|
Range of ambient temperatures (min/max) |
-40 / 80 °C |
|
|
According to standard |
EN 61643-11:2012, IEC
61643-11:2011 |
|
|
ETIM Class |
EC000381 |
|
|
Plug module |
FLP-A100N V/0 |
|
|
Customs tariff number |
85363090 |
|
|
EAN |
8595090535744 |
Lightning current arrester between N and PE , TT system,100 kA (10/350 µs)
- Brand: SALTEK - Czech Republic Categories Surge Protection Devices
- Product Code: FLP-A100N VS/NPE
- MPN: FLP-A100N VS/NPE
Terms & Conditions
All prices are subject to confirmation and exclude applicable taxes unless otherwise stated. Payment terms are as agreed in the quotation or invoice. Orders will be processed only after payment confirmation or receipt of an approved purchase order, where applicable. Dafnia reserves the right to modify product pricing, availability, and payment terms without prior notice.
Related Product
Heavy Duty 400V Surge Protected Office Power Outlet Strip
Specifications: Combi ON-OFF switch with integrated signal light Optimal user protection ..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications:Parameter name Parameter valu..