Pluggable module, line separated from protective earth via GDT.
- Lightning current arrester of two 2/3-core signalling lines.
- Installation at the boundary of LPZ 0 and LPZ 1 zones at the line entry into building.
- Mainly for protection of telecommunication lines against surge voltage.
Specifications:
Parameter name | Parameter value | |
Type of SPD | D1,C2 | |
Location of SPD | ST 1 | |
Mounting | DIN rail 35 mm | |
Maximum operating voltage | Uc | 50.00 V AC |
Maximum operating voltage | Uc | 70.00 V DC |
Nominal load current | IL | 1.600 A |
Treshold frequency core-core | f | 120.00 MHz |
D1 impulse discharge current (10/350 µs) per core | Iimp | 2.50 kA |
D1 total discharge current (10/350 µs) cores-PE | ITotal | 5.00 kA |
C2 nominal discharge current (8/20 µs) per core | In | 10.00 kA |
C2 total discharge current (8/20 µs) cores-PE | ITotal | 20.00 kA |
C3 voltage protection level mode core-PE at 1 kV/µs | Up | 550 V |
C3 voltage protection level mode core-core at 1 kV/µs | Up | 550 V |
Response time core-core | ta | 100 ns |
Response time core-PE | ta | 100 ns |
Connection (input - output) | terminals-terminals | |
Cross-section of connected conductors solid (max) | 6.00 mm2 | |
Cross-section of connected conductors stranded (max) | 6.00 mm2 | |
Degree of protection | IP 20 | |
Range of ambient temperatures (min/max) | -40 / 70 °C | |
According to standard | EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012 | |
ETIM Class | EC001466 | |
Customs tariff number | 85363030 | |
EAN | 8595090558217 |
Dimensions
Datasheet:
Lightning current arrester for signalling lines, max. 70 V
- Brand: SALTEK - Czech Republic Categories Surge Protection Devices
- Product Code: BD-090-T
- MPN: BD-090-T
Terms & Conditions
All prices are subject to confirmation and exclude applicable taxes unless otherwise stated. Payment terms are as agreed in the quotation or invoice. Orders will be processed only after payment confirmation or receipt of an approved purchase order, where applicable. Dafnia reserves the right to modify product pricing, availability, and payment terms without prior notice.
Related Product
Heavy Duty 400V Surge Protected Office Power Outlet Strip
Specifications: Combi ON-OFF switch with integrated signal light Optimal user protection ..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications:Parameter name Parameter valu..