• Module with surge protection for additional installation, acoustic fault signalling.

Acoustic fault signalling.

  • SPD for additional installation to devices or equipments.
  • Installation to LV installations, close to protected equipment.
  • For protection of all LV equipments against surge voltage.
  • Non-symetrical connection.

Specifications:


Parameter name

Parameter value

Type of SPD

T3

Mounting

installation box

Nominal voltage

Un

230 V AC

Maximum operating voltage L-N

Uc

275.00 V AC

Maximum operating voltage N-PE

Uc

255.00 V AC

Type of network

TN|TT

Maximum overcurrent protection

B 16 A

Short-circuit current rating

ISCCR

1.5 kA

Nominal discharge current (8/20 µs) L-N

In

3.00 kA

Nominal discharge current (8/20 µs) N-PE

In

6.00 kA

Test voltage L-N

Uoc

6.0 kV

Test voltage N-PE

Uoc

12.0 kV

Voltage protection level mode L-N

Up

1.45 kV

Voltage protection level mode N-PE

Up

1.50 kV

Response time L-N

ta

25 ns

Response time N-PE

ta

100 ns

TOV 5 s L-N

335 V

TOV 5 s L-PE

440 V

TOV characteristic (TOV 5 s)

withstand

TOV 120 min L-N

440 V

TOV characteristic (120 min)

withstand

TOV 200 ms L-PE

1 455 V

TOV 200 ms N-PE

1 200 V

TOV characteristic (TOV 200 ms)

safe failure

Fault indication

acoustic signalling

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-20 / 70 °C

According to standard

EN 61643-11:2012, IEC 61643-11:2011

ETIM Class

EC000942

Customs tariff number

85363010

EAN

8595090567370



Dimensions:



Write a review

Note: HTML is not translated!
Captcha

Module with surge protection for additional installation, acoustic fault signalling.

* Required fields


Terms & Conditions

All prices are subject to confirmation and exclude applicable taxes unless otherwise stated. Payment terms are as agreed in the quotation or invoice. Orders will be processed only after payment confirmation or receipt of an approved purchase order, where applicable. Dafnia reserves the right to modify product pricing, availability, and payment terms without prior notice.


Related Product

Heavy Duty 400V Surge Protected Office Power Outlet Strip

Heavy Duty 400V Surge Protected Office Power Outlet Strip

Specifications: Combi ON-OFF switch with integrated signal light Optimal user protection ..

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.

Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.

Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..

Replacement module for FLP-PV700 V/U.

Replacement module for FLP-PV700 V/U.

Replacement module for FLP-PV700 V/U.Specifications:Parameter name Parameter valu..