Pluggable module, visual fault signalling, module locking, terminals for supply, onto 40 mm busbar system.
- High performance lightning current arrester, installation at the boundary of zones LPZ 0 and LPZ 1 or higher, mainly to main distribution boards upstream power meters.
- For protection against impact of direct or indirect lightning strikes in wide range of applications – houses, office or industrial buildings, resp. to sub-distribution boards in large buildings.
- Protected supply of power meters assembly.
Specifications:
Parameter name |
Parameter
value |
|
|
Type of SPD |
T1,T2,T3 |
|
|
Mounting |
40
mm busbar system |
|
|
Nominal voltage |
Un |
230
V AC |
|
Maximum operating voltage L-N |
Uc |
255.00
V AC |
|
Maximum operating voltage N-PE |
Uc |
255.00
V AC |
|
Nominal load current - auxiliary output
terminals L, N |
6.3
A |
|
|
Type of network |
TT|TN-S |
|
|
Maximum overcurrent protection |
160
A gL/gG |
|
|
Short-circuit current rating |
ISCCR |
25.0
kA |
|
Total discharge current (10/350 µs) |
ITotal(10/350) |
30.00
kA |
|
Lightning impulse current (10/350
µs) L-N |
Iimp |
7.50
kA |
|
Lightning impulse current (10/350
µs) N-PE |
Iimp |
50.00
kA |
|
Nominal discharge current (8/20 µs)
L-N |
In |
20.00
kA |
|
Nominal discharge current (8/20 µs)
N-PE |
In |
50.00
kA |
|
Test voltage |
Uoc |
10.0
kV |
|
Total discharge current (8/20 µs) |
ITotal(8/20) |
100.00
kA |
|
Maximum discharge current (8/20 µs)
L-N |
Imax |
60.00
kA |
|
Maximum discharge current (8/20 µs)
N-PE |
Imax |
100.00
kA |
|
Voltage protection level mode L-N |
Up |
1.50
kV |
|
Voltage protection level mode L-PE |
Up |
1.50
kV |
|
Voltage protection level mode N-PE |
Up |
1.50
kV |
|
Response time L-N |
ta |
100
ns |
|
Response time N-PE |
ta |
100
ns |
|
TOV 5 s L-N |
335
V |
|
|
TOV 5 s L-PE |
440
V |
|
|
TOV characteristic (TOV 5 s) |
withstand |
|
|
TOV 120 min L-N |
440
V |
|
|
TOV 120 min L-PE |
335
V |
|
|
TOV characteristic (120 min) |
withstand |
|
|
TOV 200 ms N-PE |
1
200 V |
|
|
TOV characteristic (TOV 200 ms) |
withstand |
|
|
Cross-section of connected
conductors solid (min) |
1.00
mm2 |
|
|
Cross-section of connected
conductors solid (max) |
16.00
mm2 |
|
|
Cross-section of connected
conductors stranded (min) |
1.00
mm2 |
|
|
Cross-section of connected conductors
stranded (max) |
16.00
mm2 |
|
|
Cross-section of connected
conductors solid (max) - aux. out terminals L, N |
4.00
mm2 |
|
|
Cross-section of connected
conductors stranded (max) - aux. out terminals L, N |
2.50
mm2 |
|
|
Fault indication |
red
indication field |
|
|
Degree of protection |
IP
20 |
|
|
Range of ambient temperatures
(min/max) |
-40
/ 80 °C |
|
|
Humidity |
5
- 95 % |
|
|
According to standard |
EN
61643-11:2012, IEC 61643-11:2011 |
|
|
ETIM Class |
EC000381 |
|
|
Plug module |
FLP-ZP-7,5-VBH/0 |
|
|
Customs tariff number |
85363090 |
|
|
EAN |
8595090570288 |
Dimensions:
Replacement Module:
Datasheet:
Combination of lightning , TN and TT, 7,5 kA (10/350 µs)
- Brand: SALTEK - Czech Republic Categories Surge Protection Devices
- Product Code: FLP-ZP2-7,5-VBH/3+1
- MPN: FLP-ZP2-7,5-VBH/3+1
Terms & Conditions
All prices are subject to confirmation and exclude applicable taxes unless otherwise stated. Payment terms are as agreed in the quotation or invoice. Orders will be processed only after payment confirmation or receipt of an approved purchase order, where applicable. Dafnia reserves the right to modify product pricing, availability, and payment terms without prior notice.
Related Product
Heavy Duty 400V Surge Protected Office Power Outlet Strip
Specifications: Combi ON-OFF switch with integrated signal light Optimal user protection ..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications:Parameter name Parameter valu..