• Separating inductor (bridge) for coordination of SPDs, up to 32 A.
  • Coupling impedance.
  • For coordination of SPDs type 1 and 2 or type 2 and 4.

Specifications:


Parameter name

Parameter value

Mounting

DIN rail 35 mm

Nominal voltage

Un

450 V AC

Nominal load current

IL

32.000 A

Frequency

f

50 Hz

Resistance

R

4 mOhm

Inductance

L

5.40 uH

Maximum overcurrent protection

32 A gL/gG or C 32 A

Power loss at IL

3.68 W

Cross-section of connected conductors solid (max)

10.00 mm2

Cross-section of connected conductors stranded (max)

10.00 mm2

Cross-section of connected wires stranded with ferrule (max)

10.00 mm2

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 30 °C

ETIM Class

EC002496

Customs tariff number

85363030

EAN

8595090541783



Dimensions:



Datasheet:

     RTO-35


Write a review

Note: HTML is not translated!
Captcha

Separating inductor (bridge) for coordination of SPDs, up to 32 A.

* Required fields


Terms & Conditions

All prices are subject to confirmation and exclude applicable taxes unless otherwise stated. Payment terms are as agreed in the quotation or invoice. Orders will be processed only after payment confirmation or receipt of an approved purchase order, where applicable. Dafnia reserves the right to modify product pricing, availability, and payment terms without prior notice.


Related Product

Heavy Duty 400V Surge Protected Office Power Outlet Strip

Heavy Duty 400V Surge Protected Office Power Outlet Strip

Specifications: Combi ON-OFF switch with integrated signal light Optimal user protection ..

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.

Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.

Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..

Replacement module for FLP-PV700 V/U.

Replacement module for FLP-PV700 V/U.

Replacement module for FLP-PV700 V/U.Specifications:Parameter name Parameter valu..