LPZ 1 and higher, Ethernet without PoE
- Fine surge protection.
- Installation at protected device inside LPZ1 and higher (not suitable for LPZ 0).
- For pprotection of Ethernet networks (up to Cat.6A) without PoE.
- Installation into DL-PL-RACK-1U box.
- DL-...-M with front output.
- DL-...-R-M with rear output.
- Not applicable for Ethernet with PoE.
Specifications:
Parameter
name |
Parameter value |
|
|
Type of SPD |
C2,C3 |
|
|
Location of SPD |
ST 2+3 |
|
|
Mounting |
DL-PL-RACK-1U |
|
|
Maximum operating
voltage |
Uc |
6.00 V AC |
|
Maximum operating
voltage |
Uc |
8.50 V DC |
|
Maximum operating
voltage POE |
Uc |
6.00 V AC |
|
Maximum operating
voltage POE |
Uc |
8.50 V DC |
|
Nominal load current
per core at 25 °C |
IL |
0.5 A |
|
Treshold frequency
core-core |
f |
500.00 MHz |
|
Insertion attenuation
at treshhold frequency |
2.90 dB |
|
|
C2 nominal discharge
current (8/20 µs) per core |
In |
0.20 kA |
|
C2 total discharge
current (8/20 µs) cores-PE |
ITotal |
1.60 kA |
|
C2 voltage protection
level mode (POE) at In |
Up |
55.00 V |
|
C2 voltage protection
level mode core-PE at In |
Up |
400 V |
|
C2 voltage protection
level mode core-core at In |
Up |
55 V |
|
C3 voltage protection
level mode (POE) at 1 kV/µs |
30.00 V |
|
|
C3 voltage protection
level mode core-PE at 1 kV/µs |
Up |
600 V |
|
C3 voltage protection
level mode core-core at 1 kV/µs |
Up |
30 V |
|
Response time
core-core |
ta |
1 ns |
|
Response time core-PE |
ta |
100 ns |
|
Connection (input -
output) |
RJ 45/RJ 45 |
|
|
Degree of protection |
IP 20 |
|
|
Range of ambient
temperatures (min/max) |
-40 / 80 °C |
|
|
Humidity |
5 - 95 % |
|
|
According to standard |
EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012 |
|
|
Customs tariff number |
85363010 |
|
|
EAN |
8595090541844 |
Dimensions:
Datasheet:
SPD for high-speed Ethernet networks, LPZ 1 and higher
- Brand: SALTEK - Czech Republic Categories Surge Protection Devices
- Product Code: DL-Cat.6A-R-M
- MPN: DL-Cat.6A-R-M
Terms & Conditions
All prices are subject to confirmation and exclude applicable taxes unless otherwise stated. Payment terms are as agreed in the quotation or invoice. Orders will be processed only after payment confirmation or receipt of an approved purchase order, where applicable. Dafnia reserves the right to modify product pricing, availability, and payment terms without prior notice.
Related Product
Heavy Duty 400V Surge Protected Office Power Outlet Strip
Specifications: Combi ON-OFF switch with integrated signal light Optimal user protection ..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications:Parameter name Parameter valu..