Coupling impedance (resistance), screw
terminals.
- Coarse and fine surge
protection for 2-core signalling networks.
- Installation close to
protected equipment.
- For protection of
communication interfaces, mainly the RS-485 lines, of I&C, electronic
security and fire detection systems, etc. against impact of surge voltage.
- Coarse and fine surge protection in differential mode (core – core) and common mode (core – PE).
Specifications:
|
Parameter name |
Parameter value |
|
|
Type of SPD |
C2,C3 |
|
|
Location of
SPD |
ST 2+3 |
|
|
Mounting |
DIN rail 35 mm |
|
|
Nominal
voltage |
Un |
60 V DC |
|
Maximum
operating voltage |
Uc |
45.00 V AC |
|
Maximum
operating voltage |
Uc |
64.00 V DC |
|
Nominal
load current |
IL |
0.500 A |
|
Treshold
frequency core-core |
f |
6.50 MHz |
|
Serial
resistance per core |
R |
1.60 Ω |
|
D1 impulse
discharge current (10/350 µs) per core |
Iimp |
0.50 kA |
|
D1 total
discharge current (10/350 µs) cores-PE |
ITotal |
1.00 kA |
|
C2 nominal
discharge current (8/20 µs) per core |
In |
5.00 kA |
|
C2 total
discharge current (8/20 µs) cores-PE |
ITotal |
10.00 kA |
|
C2 voltage
protection level mode core-PE at In |
Up |
120 V |
|
C2 voltage
protection level mode core-core at In |
Up |
100 V |
|
C3 voltage
protection level mode core-PE at 1 kV/µs |
Up |
85 V |
|
C3 voltage
protection level mode core-core at 1 kV/µs |
Up |
85 V |
|
Response
time core-core |
ta |
1 ns |
|
Response
time core-PE |
ta |
1 ns |
|
Connection
(input - output) |
terminals-terminals |
|
|
Cross-section
of connected conductors solid (min) |
0.14 mm2 |
|
|
Cross-section
of connected conductors solid (max) |
4.00 mm2 |
|
|
Cross-section
of connected conductors stranded (min) |
0.14 mm2 |
|
|
Cross-section
of connected conductors stranded (max) |
2.50 mm2 |
|
|
Degree of
protection |
IP 20 |
|
|
Range of
ambient temperatures (min/max) |
-40 / 70 °C |
|
|
According
to standard |
EN 61643-21+A1,A2:2013,
IEC 61643-21+A1,A2:2012 |
|
|
ETIM Class |
EC001625 |
|
|
Customs
tariff number |
85363030 |
|
|
EAN |
8595090551294 |
Dimensions:
Datasheet:
Surge protection for 2-core signalling networks, terminal block with screw terminals, 60 V DC, max. 0.5 A
- Brand: SALTEK - Czech Republic Categories Surge Protection Devices
- Product Code: DM-060/1-RS
- MPN: DM-060/1-RS
Terms & Conditions
All prices are subject to confirmation and exclude applicable taxes unless otherwise stated. Payment terms are as agreed in the quotation or invoice. Orders will be processed only after payment confirmation or receipt of an approved purchase order, where applicable. Dafnia reserves the right to modify product pricing, availability, and payment terms without prior notice.
Related Product
Heavy Duty 400V Surge Protected Office Power Outlet Strip
Specifications: Combi ON-OFF switch with integrated signal light Optimal user protection ..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications:Parameter name Parameter valu..