• Combination of lightning current and surge arrester 3+1 for three-phase 50 kA

Pluggable module, visual fault signalling, remote fault signalling.

  • Combination of one-pole lightning current arrester and encapsulated efficiency spark gap, connected in the 3+1 mode.
  • Installation at the boundary of zones LPZ 0 and LPZ 1 or higher.
  • For protection against impact of direct or indirect lightning strikes – eg. charching stations for electrical vehicles.
  • Zero leakage current.


Specifications:


Parameter name

Parameter value

Type of SPD

T1,T2

Mounting

DIN rail 35 mm

Nominal voltage

Un

230 V AC

Maximum operating voltage L-N

Uc

275.00 V AC

Maximum operating voltage N-PE

Uc

255.00 V AC

Type of network

TT

Maximum overcurrent protection

160 A gL/gG

Short-circuit current rating

ISCCR

50.0 kA

Lightning impulse current (10/350 µs) L-N

Iimp

12.50 kA

Lightning impulse current (10/350 µs) N-PE

Iimp

50.00 kA

Nominal discharge current (8/20 µs) L-N

In

30.00 kA

Nominal discharge current (8/20 µs) N-PE

In

50.00 kA

Maximum discharge current (8/20 µs) L-N

Imax

60.00 kA

Maximum discharge current (8/20 µs) N-PE

Imax

100.00 kA

Voltage protection level mode L-N

Up

1.50 kV

Voltage protection level mode N-PE

Up

1.50 kV

Response time L-N

ta

100 ns

Response time N-PE

ta

100 ns

TOV 5 s L-N

335 V

TOV characteristic (TOV 5 s)

withstand

TOV 120 min L-N

440 V

TOV characteristic (120 min)

withstand

TOV 200 ms N-PE

1 200 V

TOV characteristic (TOV 200 ms)

withstand

Cross-section of connected conductors solid (min)

1.00 mm2

Cross-section of connected conductors solid (max)

35.00 mm2

Cross-section of connected conductors stranded (min)

1.00 mm2

Cross-section of connected conductors stranded (max)

25.00 mm2

Cross-section of remote indication conductors solid (max)

1.5 mm2

Cross-section of remote indication conductors stranded (max)

1.5 mm2

Fault indication L-N

red indication field

Remote indication

potential-free change-over contact

Remote indication contacts

250V/0,5A AC,250V/0,1A DC

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 80 °C

Humidity

5 - 95 %

According to standard

EN 61643-11:2012, IEC 61643-11:2011

ETIM Class

EC001457

Customs tariff number

85363030

EAN

8595090570493



Dimensions:



Datasheet:

     FLP-EV12,5-VBH/3S+1


Write a review

Note: HTML is not translated!
Captcha

Combination of lightning current and surge arrester 3+1 for three-phase 50 kA

* Required fields


Terms & Conditions

All prices are subject to confirmation and exclude applicable taxes unless otherwise stated. Payment terms are as agreed in the quotation or invoice. Orders will be processed only after payment confirmation or receipt of an approved purchase order, where applicable. Dafnia reserves the right to modify product pricing, availability, and payment terms without prior notice.


Related Product

Heavy Duty 400V Surge Protected Office Power Outlet Strip

Heavy Duty 400V Surge Protected Office Power Outlet Strip

Specifications: Combi ON-OFF switch with integrated signal light Optimal user protection ..

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.

Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.

Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..

Replacement module for FLP-PV700 V/U.

Replacement module for FLP-PV700 V/U.

Replacement module for FLP-PV700 V/U.Specifications:Parameter name Parameter valu..