• Combination of lightning current and surge arrester ,100 kA

Pluggable module, visual fault signalling, module locking, remote fault signalling.

  • Four-pole high performance lightning current arrester.
  • Installation at the boundary of zones LPZ 0 and LPZ 1 or higher, mainly to main distribution boards.
  • For protection against impact of direct or indirect lightning strikes in wide range of applications – office or industrial buildings.
  • No follow current, zero leakage current.
  • With integrated backup fuse.


Specifications:

Parameter name

Parameter value

Type of SPD

T1,T2

Mounting

DIN rail 35 mm

Nominal voltage

Un

230 V AC

Maximum operating voltage

Uc

260.00 V AC

Type of network

TN-S

Maximum overcurrent protection

-

Short-circuit current rating

ISCCR

50.0 kA

Lightning impulse current (10/350 µs)

Iimp

25.00 kA

Nominal discharge current (8/20 µs)

In

30.00 kA

Maximum discharge current (8/20 µs)

Imax

60.00 kA

Voltage protection level

Up

1.50 kV

Response time

ta

100 ns

TOV 5 s L-N

335 V

TOV characteristic (TOV 5 s)

withstand

TOV 120 min L-N

440 V

TOV characteristic (120 min)

withstand

Cross-section of connected conductors solid (min)

2.50 mm2

Cross-section of connected conductors solid (max)

50.00 mm2

Cross-section of connected conductors stranded (min)

2.50 mm2

Cross-section of connected conductors stranded (max)

35.00 mm2

Cross-section of remote indication conductors solid (max)

1.5 mm2

Cross-section of remote indication conductors stranded (max)

1.5 mm2

Fault indication

red indication field

Remote indication

potential-free change-over contact

Remote indication contacts

250V/0,5A AC,250V/0,1A DC

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 80 °C

Humidity

5 - 95 %

According to standard

EN 61643-11:2012, IEC 61643-11:2011

ETIM Class

EC001457

Plug module

FLP-B+C MAXI V/0

Customs tariff number

85363090

EAN

8595090571193


Dimensions:


Replacement module: FLP-B+C MAXI V/0



Write a review

Note: HTML is not translated!
Captcha

Combination of lightning current and surge arrester ,100 kA

0 reviews / Write a review

* Required fields



Related Product

AC diverter ,for suppression of AC voltage

AC diverter ,for suppression of AC voltage

SPD for Cathodic Corrosion Protection System.Combines an AC current diverter and a SPD in one enclos..

Digital tester for status monitor of SPDs

Digital tester for status monitor of SPDs

Measurement of insulation resistance. It can be used to provide a more accurate imagine of the SPD s..

Automatic VLD class 2 tester

Automatic VLD class 2 tester

Portable automatic tester of VLD class 2.Fully automatic measurement.Measurement of Non-triggering v..

Voltage limiting device, VLD of class 2.2, type VLD-O+F

Voltage limiting device, VLD of class 2.2, type VLD-O+F

Voltage limiting device, VLD of class 2.2, type VLD-O+F, limiting of occurrence non-permissible touc..