Pluggable
module, visual fault signalling, module locking, remote fault signalling.
- Four-pole
high performance lightning current arrester.
- Installation
at the boundary of zones LPZ 0 and LPZ 1 or higher, mainly to main distribution
boards.
- For
protection against impact of direct or indirect lightning strikes in wide range
of applications – office or industrial buildings.
- No
follow current, zero leakage current.
- With integrated backup fuse.
Specifications:
Parameter name |
Parameter
value |
||
Type of SPD |
T1,T2 |
||
Mounting |
DIN
rail 35 mm |
||
Nominal voltage |
Un |
230
V AC |
|
Maximum operating voltage |
Uc |
260.00
V AC |
|
Type of network |
TN-S |
||
Maximum overcurrent protection |
- |
||
Short-circuit current rating |
ISCCR |
50.0
kA |
|
Lightning impulse current (10/350
µs) |
Iimp |
25.00
kA |
|
Nominal discharge current (8/20 µs) |
In |
30.00
kA |
|
Maximum discharge current (8/20 µs) |
Imax |
60.00
kA |
|
Voltage protection level |
Up |
1.50
kV |
|
Response time |
ta |
100
ns |
|
TOV 5 s L-N |
335
V |
||
TOV characteristic (TOV 5 s) |
withstand |
||
TOV 120 min L-N |
440
V |
||
TOV characteristic (120 min) |
withstand |
||
Cross-section of connected
conductors solid (min) |
2.50
mm2 |
||
Cross-section of connected
conductors solid (max) |
50.00
mm2 |
||
Cross-section of connected
conductors stranded (min) |
2.50
mm2 |
||
Cross-section of connected conductors
stranded (max) |
35.00
mm2 |
||
Cross-section of remote indication
conductors solid (max) |
1.5
mm2 |
||
Cross-section of remote indication
conductors stranded (max) |
1.5
mm2 |
||
Fault indication |
red
indication field |
||
Remote indication |
potential-free
change-over contact |
||
Remote indication contacts |
250V/0,5A
AC,250V/0,1A DC |
||
Degree of protection |
IP
20 |
||
Range of ambient temperatures
(min/max) |
-40
/ 80 °C |
||
Humidity |
5
- 95 % |
||
According to standard |
EN
61643-11:2012, IEC 61643-11:2011 |
||
ETIM Class |
EC001457 |
||
Plug module |
FLP-B+C
MAXI V/0 |
||
Customs tariff number |
85363090 |
||
EAN |
8595090571193 |
Dimensions:
Replacement module: FLP-B+C MAXI V/0
Combination of lightning current and surge arrester ,100 kA
Related Product
AC diverter ,for suppression of AC voltage
SPD for Cathodic Corrosion Protection System.Combines an AC current diverter and a SPD in one enclos..
Digital tester for status monitor of SPDs
Measurement of insulation resistance. It can be used to provide a more accurate imagine of the SPD s..
Automatic VLD class 2 tester
Portable automatic tester of VLD class 2.Fully automatic measurement.Measurement of Non-triggering v..
Voltage limiting device, VLD of class 2.2, type VLD-O+F
Voltage limiting device, VLD of class 2.2, type VLD-O+F, limiting of occurrence non-permissible touc..