• Surge protection for Ethernet without PoE, Cat.6A, LPZ1 and higher

RJ45 sockets1.

  • Fine surge protection of Ethernet line.
  • Installation close to protected equipment.
  • For protection of Ethernet line Cat. 6A against surge voltage.
  • In the scope of delivery: universal plastic adapter for mounting on DIN rail and GND 2 holder.


Specifications:

Parameter name

Parameter value

Type of SPD

C2,C3

Location of SPD

ST 2+3

Mounting

DIN rail 35 mm

Maximum operating voltage

Uc

6.00 V AC

Maximum operating voltage

Uc

8.50 V DC

Maximum operating voltage POE

Uc

6.00 V AC

Maximum operating voltage POE

Uc

8.50 V DC

Nominal load current per core at 25 °C

IL

0.5 A

Treshold frequency core-core

f

500.00 MHz

Insertion attenuation at treshhold frequency

2.90 dB

C2 nominal discharge current (8/20 µs) per core

In

0.20 kA

C2 total discharge current (8/20 µs) cores-PE

ITotal

1.60 kA

C2 voltage protection level mode (POE) at In

Up

55.00 V

C2 voltage protection level mode core-PE at In

Up

400 V

C2 voltage protection level mode core-core at In

Up

55 V

C3 voltage protection level mode (POE) at 1 kV/µs

30.00 V

C3 voltage protection level mode core-PE at 1 kV/µs

Up

600 V

C3 voltage protection level mode core-core at 1 kV/µs

Up

30 V

Response time core-core

ta

1 ns

Response time core-PE

ta

100 ns

Connection (input - output)

RJ45/RJ45

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 80 °C

Humidity

5 - 95 %

According to standard

EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012

ETIM Class

EC000943

Customs tariff number

85363030

EAN

8595090565741


Dimensions:


Datasheet:

     DL-Cat.6A

Write a review

Note: HTML is not translated!
Captcha

Surge protection for Ethernet without PoE, Cat.6A, LPZ1 and higher

* Required fields


Terms & Conditions

All prices are subject to confirmation and exclude applicable taxes unless otherwise stated. Payment terms are as agreed in the quotation or invoice. Orders will be processed only after payment confirmation or receipt of an approved purchase order, where applicable. Dafnia reserves the right to modify product pricing, availability, and payment terms without prior notice.


Related Product

Heavy Duty 400V Surge Protected Office Power Outlet Strip

Heavy Duty 400V Surge Protected Office Power Outlet Strip

Specifications: Combi ON-OFF switch with integrated signal light Optimal user protection ..

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.

Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.

Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..

Replacement module for FLP-PV700 V/U.

Replacement module for FLP-PV700 V/U.

Replacement module for FLP-PV700 V/U.Specifications:Parameter name Parameter valu..