• Combined type surge ,TN and TT systems ,75 V AC, 25 kA (8/20 µs)

Pluggable module, visual fault signalling.

  • Combined type surge arrester (serial combination varistor+GDT).
  • Installation to LV installations, especially to sub-distribution boards, suitable also for measuring circuits.
  • For protection of the installations and equipments against impact of induced overvoltages during a lightning strike in areas with higher storm activity or switching overvoltages or as the first stage of for protection for measuring circuits.
  • No leakage current.


Specifications:


Parameter name

Parameter value

Type of SPD

T2

Mounting

DIN rail 35 mm

Maximum operating voltage

Uc

75.00 V AC

Maximum operating voltage

Uc

100.00 V DC

Type of network

TN

Maximum overcurrent protection

125 A gL/gG

Short-circuit current rating

ISCCR

35.0 kA

Nominal discharge current (8/20 µs)

In

15.00 kA

Maximum discharge current (8/20 µs)

Imax

25.00 kA

Voltage protection level

Up

0.60 kV

Voltage protection level at 5 kA

Up

0.30 kV

Response time

ta

100 ns

Cross-section of connected conductors solid (min)

1.00 mm2

Cross-section of connected conductors solid (max)

35.00 mm2

Cross-section of connected conductors stranded (min)

1.00 mm2

Cross-section of connected conductors stranded (max)

25.00 mm2

Fault indication

red indication field

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 80 °C

Humidity

5 - 95 %

According to standard

EN 61643-11:2012, IEC 61643-11:2011

ETIM Class

EC000941

Plug module

SLP-075 VB/0

Customs tariff number

85363030

EAN

8595090521556


Dimensions:





Replacement module: SLP-075 VB/0







Write a review

Note: HTML is not translated!
Captcha

Combined type surge ,TN and TT systems ,75 V AC, 25 kA (8/20 µs)

* Required fields


Terms & Conditions

All prices are subject to confirmation and exclude applicable taxes unless otherwise stated. Payment terms are as agreed in the quotation or invoice. Orders will be processed only after payment confirmation or receipt of an approved purchase order, where applicable. Dafnia reserves the right to modify product pricing, availability, and payment terms without prior notice.


Related Product

Heavy Duty 400V Surge Protected Office Power Outlet Strip

Heavy Duty 400V Surge Protected Office Power Outlet Strip

Specifications: Combi ON-OFF switch with integrated signal light Optimal user protection ..

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.

Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.

Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..

Replacement module for FLP-PV700 V/U.

Replacement module for FLP-PV700 V/U.

Replacement module for FLP-PV700 V/U.Specifications:Parameter name Parameter valu..