Pluggable module, visual fault signalling, remote fault signalling.
- Combination of combined type surge arrester (serial combination varistor+GDT) and encapsulated spark gap, connected in the 3+1 mode.
- Installation to LV installations, especially to sub-distribution boards in areas with unstable grid voltage and where diesel generators are used, suitable also for measuring circuits.
- For protection of the installations and equipments against impact of induced overvoltages during a lightning strike in areas with higher storm activity or switching overvoltages or as the first stage of for protection for measuring circuits.
- Zero leakage current.
Specifications:
|
Parameter name |
Parameter value |
|
|
Type
of SPD |
T2 |
|
|
Mounting |
DIN rail 35 mm |
|
|
Nominal
voltage |
Un |
230/400 V AC |
|
Maximum
operating voltage L-N |
Uc |
275.00 V AC |
|
Maximum
operating voltage N-PE |
Uc |
255.00 V AC |
|
Type
of network |
TN-S|TT |
|
|
Maximum
overcurrent protection |
125 A gL/gG |
|
|
Short-circuit
current rating |
ISCCR |
50.0 kA |
|
Residual
current |
IPE |
0.002 mA |
|
Nominal
discharge current (8/20 µs) |
In |
20.00 kA |
|
Maximum
discharge current (8/20 µs) |
Imax |
40.00 kA |
|
Voltage
protection level mode L-N |
Up |
1.50 kV |
|
Voltage
protection level mode L-PE |
Up |
2.50 kV |
|
Voltage
protection level mode N-PE |
Up |
1.50 kV |
|
Ability
to independently switch off the following current N-PE |
Ifi |
0.1 kA |
|
Response
time |
ta |
100 ns |
|
TOV
5 s L-N |
335 V |
|
|
TOV
characteristic (TOV 5 s) |
withstand |
|
|
TOV
120 min L-N |
440 V |
|
|
TOV
characteristic (120 min) |
withstand |
|
|
TOV
200 ms L-PE |
1 455 V |
|
|
TOV
200 ms N-PE |
1 200 V |
|
|
TOV
characteristic (TOV 200 ms) |
withstand |
|
|
Cross-section
of connected conductors solid (min) |
1.00 mm2 |
|
|
Cross-section
of connected conductors solid (max) |
35.00 mm2 |
|
|
Cross-section
of connected conductors stranded (min) |
1.00 mm2 |
|
|
Cross-section
of connected conductors stranded (max) |
25.00 mm2 |
|
|
Cross-section
of remote indication conductors solid (max) |
1.5 mm2 |
|
|
Cross-section
of remote indication conductors stranded (max) |
1.5 mm2 |
|
|
Fault
indication |
red indication field |
|
|
Remote
indication |
potential-free change-over contact |
|
|
Remote
indication contacts |
250V/0,5A AC,250V/0,1A DC |
|
|
Degree
of protection |
IP 20 |
|
|
Range
of ambient temperatures (min/max) |
-40 / 80 °C |
|
|
Humidity |
5 - 95 % |
|
|
According
to standard |
EN 61643-11:2012, IEC 61643-11:2011 |
|
|
ETIM
Class |
EC000941 |
|
|
Plug
module |
SLP-275-VB/0|SLP-NPE V/0 |
|
|
Customs
tariff number |
85363030 |
|
|
EAN |
8595090570608 |
Dimensions:
Combined type surge arrester,TN-S and TT systems, 40 kA (8/20 µs)
- Brand: SALTEK - Czech Republic Categories Surge Protection Devices
- Product Code: SLP-275-VB/3S+1
- MPN: SLP-275-VB/3S+1
Terms & Conditions
All prices are subject to confirmation and exclude applicable taxes unless otherwise stated. Payment terms are as agreed in the quotation or invoice. Orders will be processed only after payment confirmation or receipt of an approved purchase order, where applicable. Dafnia reserves the right to modify product pricing, availability, and payment terms without prior notice.
Related Product
Heavy Duty 400V Surge Protected Office Power Outlet Strip
Specifications: Combi ON-OFF switch with integrated signal light Optimal user protection ..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications:Parameter name Parameter valu..