Visual
fault signalling.
- Varistor
lightning current arrester and surge arrester in 'Y' connection.
- For
protection of PV systems on the roofs, where the separating spark-over distance
is not kept (connection to LPS).
- Maximum continuous operating voltage for PV application: UCPV ≥ 1.2x UOC STC.
Specifications:
|
Parameter name |
Parameter value |
|
|
Type of SPD |
PV T1,
PV T2 |
|
|
Mounting |
DIN rail
35 mm |
|
|
Maximum operating voltage mode +/PE, -/PE |
UCPV |
1 500.00
V DC |
|
Short-circuit current rating |
ISCPV |
10 000 A
DC |
|
Residual current mode +/PE, -/PE |
IPE |
1.000 mA
AC |
|
Residual current mode +/PE, -/PE |
IPE |
0.010 mA
DC |
|
Total discharge current (10/350 µs) |
ITotal(10/350) |
12.50 kA |
|
Lightning impulse current (10/350 µs) |
Iimp |
6.25 kA |
|
Total discharge current (8/20 µs) |
ITotal(8/20) |
80.00 kA |
|
Nominal discharge current (8/20 µs) |
In |
20.00 kA |
|
Maximum discharge current (8/20 µs) |
Imax |
40.00 kA |
|
Voltage protection level mode +/- |
Up |
5.40 kV |
|
Voltage protection level mode +/PE, -/PE |
Up |
5.40 kV |
|
Response time |
ta |
25 ns |
|
Cross-section of connected conductors solid (min) |
4.00 mm2 |
|
|
Cross-section of connected conductors solid (max) |
35.00 mm2 |
|
|
Cross-section of connected conductors stranded (min) |
2.50 mm2 |
|
|
Cross-section of connected conductors stranded (max) |
25.00 mm2 |
|
|
Fault indication |
red
indication field |
|
|
Degree of protection |
IP 20 |
|
|
Range of ambient temperatures (min/max) |
-40 / 80
°C |
|
|
According to standard |
EN 61643-31,
IEC 61643-31 |
|
|
ETIM Class |
EC001457 |
|
|
Customs tariff number |
85363090 |
|
|
EAN |
8595090542001 |
Dimensions:
Lightning current and surge arrester for PV systems,1500 V DC
Related Product
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications: Parameter name ..
Replacement module for SLP-PV500 V/U.
Replacement module for SLP-PV1000 V/Y (S).Specifications: Parameter name ..





