Pluggable module, visual fault signalling, module locking, remote fault signalling.
- Combination of varistor lightning current arrester and encapsulated efficiency spark gap, connected in the 1+1 mode.
- Installation at the boundary of zones LPZ 0 and LPZ 1 or higher, for objects in LPL III and IV.
- For protection against impact of partial lightning currents, induced overvoltages during a lightning strike or switching overvoltages.
Specifications:
Parameter name |
Parameter
value |
|
|
Type of SPD |
T1,T2 |
|
|
Mounting |
DIN
rail 35 mm |
|
|
Nominal voltage |
Un |
230
V AC |
|
Maximum operating voltage L-N |
Uc |
275.00
V AC |
|
Maximum operating voltage N-PE |
Uc |
255.00
V AC |
|
Type of network |
TT |
|
|
Maximum overcurrent protection |
160
A gL/gG |
|
|
Short-circuit current rating |
ISCCR |
50.0
kA |
|
Total discharge current (10/350 µs) |
ITotal(10/350) |
25.00
kA |
|
Lightning impulse current (10/350
µs) L-N |
Iimp |
12.50
kA |
|
Lightning impulse current (10/350
µs) N-PE |
Iimp |
25.00
kA |
|
Nominal discharge current (8/20 µs)
L-N |
In |
30.00
kA |
|
Nominal discharge current (8/20 µs)
N-PE |
In |
30.00
kA |
|
Maximum discharge current (8/20 µs)
L-N |
Imax |
60.00
kA |
|
Maximum discharge current (8/20 µs)
N-PE |
Imax |
60.00
kA |
|
Voltage protection level mode L-N |
Up |
1.50
kV |
|
Voltage protection level mode L-PE |
Up |
1.50
kV |
|
Voltage protection level mode N-PE |
Up |
1.50
kV |
|
Voltage protection level at 5 kA L-N |
Up |
0.90
kV |
|
Ability to independently switch off
the following current N-PE |
Ifi |
100.0
kA |
|
Response time L-N |
ta |
25
ns |
|
Response time N-PE |
ta |
100
ns |
|
TOV 5 s L-N |
335
V |
|
|
TOV characteristic (TOV 5 s) |
withstand |
|
|
TOV 200 ms N-PE |
1
200 V |
|
|
TOV characteristic (TOV 200 ms) |
withstand |
|
|
Cross-section of connected
conductors solid (min) |
1.00
mm2 |
|
|
Cross-section of connected
conductors solid (max) |
35.00
mm2 |
|
|
Cross-section of connected
conductors stranded (min) |
1.00
mm2 |
|
|
Cross-section of connected
conductors stranded (max) |
25.00
mm2 |
|
|
Cross-section of remote indication
conductors solid (max) |
1.5
mm2 |
|
|
Cross-section of remote indication
conductors stranded (max) |
1.5
mm2 |
|
|
Fault indication L-N |
red
indication field |
|
|
Remote indication |
potential-free
change-over contact |
|
|
Remote indication contacts |
250V/0,5A
AC,250V/0,1A DC |
|
|
Degree of protection |
IP
20 |
|
|
Range of ambient temperatures
(min/max) |
-40
/ 80 °C |
|
|
Humidity |
5
- 95 % |
|
|
According to standard |
EN
61643-11:2012, IEC 61643-11:2011 |
|
|
ETIM Class |
EC001457 |
|
|
Plug module |
FLP-12,5
V/0|FLP-NPE 25 V/0 |
|
|
Customs tariff number |
85363090 |
|
|
EAN |
8595090534242 |
Dimensions:
Datasheet:
Lightning current and surge arrester, 25 kA
- Brand: SALTEK - Czech Republic Categories Surge Protection Devices
- Product Code: FLP-12,5 V/1S+1
- MPN: FLP-12,5 V/1S+1
Terms & Conditions
All prices are subject to confirmation and exclude applicable taxes unless otherwise stated. Payment terms are as agreed in the quotation or invoice. Orders will be processed only after payment confirmation or receipt of an approved purchase order, where applicable. Dafnia reserves the right to modify product pricing, availability, and payment terms without prior notice.
Related Product
Heavy Duty 400V Surge Protected Office Power Outlet Strip
Specifications: Combi ON-OFF switch with integrated signal light Optimal user protection ..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications:Parameter name Parameter valu..