Pluggable module, coupling impedance (R – resistance),
line separated from protective earth via GDT.
- Lightning current arrester with coarse and
fine surge protection for 2-core signalling lines.
- Installation at the boundary of LPZ 0 and LPZ
1 zones or higher, at the line entry into building and also installation close
to protected device.
- For protection of telecommunication line
against impact of surge voltage
- Coarse and fine surge protection (core –
core) in differential mode and coarse surge protection in common mode (line –
PE).
Specifications:
Parameter name | Parameter
value | |
Type of SPD | D1,C2 | |
Location of SPD | ST 1+2+3 | |
Mounting | DIN rail 35 mm | |
Nominal voltage | Un | 230 V DC |
Maximum operating voltage | Uc | 177.00 V AC |
Maximum operating voltage | Uc | 250.00 V DC |
Nominal load current | IL | 1.000 A |
Treshold frequency core-core | f | 16.00 MHz |
Serial resistance per core | R | 1.60 Ω |
D1 impulse discharge current
(10/350 µs) per core | Iimp | 2.50 kA |
D1 total discharge current
(10/350 µs) cores-PE | ITotal | 5.00 kA |
C2 nominal discharge current
(8/20 µs) GND-PE | In | 10.00 kA |
C2 nominal discharge current
(8/20 µs) per core | In | 10.00 kA |
C2 total discharge current
(8/20 µs) cores-PE | ITotal | 20.00 kA |
C3 nominal discharge current
(10/1000 µs) core-PE | ISM | 10 A |
C3 nominal discharge current
(10/1000 µs) core-core | ISM | 10 A |
C3 voltage protection level
mode GND-PE at 1 kV/µs | Up | 550.00 V |
C3 voltage protection level
mode core-GND at 1 kV/µs | Up | 550.00 V |
C3 voltage protection level
mode core-core at 1 kV/µs | Up | 350 V |
Response time core-core | ta | 1 ns |
Response time core-GND | ta | 100 ns |
Response time GND-PE | ta | 100 ns |
Connection (input - output) | terminals-terminals | |
Cross-section of connected
conductors solid (min) | 0.14 mm2 | |
Cross-section of connected
conductors solid (max) | 4.00 mm2 | |
Cross-section of connected
conductors stranded (min) | 0.14 mm2 | |
Cross-section of connected
conductors stranded (max) | 2.50 mm2 | |
Degree of protection | IP 20 | |
Range of ambient temperatures
(min/max) | -40 / 70 °C | |
According to standard | EN 61643-21+A1,A2:2013, IEC
61643-21+A1,A2:2012 | |
ETIM Class | EC001625 | |
Plug module | BDG-230-V/1-0 | |
Customs tariff number | 85363010 | |
EAN | 8595090565147 |
Dimensions:
Replacement module: BDG-230-V/1-0
Lightning current arrester replacement module, for 2-core signalling lines, 230 V DC, max. 1 A
Related Product
Lightning current arrester replacement module for 2-core signalling lines, 6 V DC, max. 2 A
Pluggable module, coupling impedance (R – resistance), line separated from protective earth via GDT..
Lightning current arrester replacement module, for 2-core signalling lines, 230 V DC, max. 1 A
Pluggable module, coupling impedance (R – resistance), line separated from protective earth via GDT..
Lightning current arrester for shielded 2-core signalling lines, 230 V DC, max. 0.
Pluggable module, coupling impedance (R – resistance), line separated from protective earth via GDT..
Lightning current arrester replacement module, for 2-core signalling lines, 60 V DC, max. 1 A
Pluggable module, coupling impedance (R – resistance), line separated from protective earth via GD..