Pluggable module, coupling impedance (R – resistance),
line separated from protective earth via GDT.
- Lightning current arrester with coarse and
fine surge protection for 2-core signalling lines.
- Installation at the boundary of LPZ 0 and LPZ
1 zones or higher, at the line entry into building and also installation close
to protected device.
- For protection of communication interfaces of
I&C, MaR systems, electronic security and fire detection systems, etc.
(mainly for RS-485 inter- faces) against impact of surge voltage.
- Coarse and fine surge protection (core – core) in differential mode and coarse surge protection in common mode (line – PE).
Specifications:
| Parameter name | Parameter
   value | |
| Type of SPD | D1,C2 | |
| Location of SPD | ST 1+2+3 | |
| Mounting | DIN rail 35 mm | |
| Nominal voltage | Un | 6 V DC | 
| Maximum operating voltage | Uc | 6.00 V AC | 
| Maximum operating voltage | Uc | 8.50 V DC | 
| Nominal load current | IL | 2.000 A | 
| Treshold frequency core-core | f | 1.20 MHz | 
| Serial resistance per core | R | 0.40 Ω | 
| D1 impulse discharge current
  (10/350 µs) per core | Iimp | 2.50 kA | 
| D1 total discharge current
  (10/350 µs) cores-PE | ITotal | 5.00 kA | 
| C2 nominal discharge current
  (8/20 µs) GND-PE | In | 10.00 kA | 
| C2 nominal discharge current
  (8/20 µs) per core | In | 10.00 kA | 
| C2 total discharge current
  (8/20 µs) cores-PE | ITotal | 20.00 kA | 
| C3 nominal discharge current
  (10/1000 µs) core-PE | ISM | 10 A | 
| C3 nominal discharge current
  (10/1000 µs) core-core | ISM | 10 A | 
| C3 voltage protection level
  mode GND-PE at 1 kV/µs | Up | 550.00 V | 
| C3 voltage protection level
  mode core-GND at 1 kV/µs | Up | 550.00 V | 
| C3 voltage protection level
  mode core-core at 1 kV/µs | Up | 12 V | 
| Response time core-core | ta | 1 ns | 
| Response time core-GND | ta | 100 ns | 
| Response time GND-PE | ta | 100 ns | 
| Connection (input - output) | terminals-terminals | |
| Cross-section of connected
  conductors solid (min) | 0.14 mm2 | |
| Cross-section of connected
  conductors solid (max) | 4.00 mm2 | |
| Cross-section of connected
  conductors stranded (min) | 0.14 mm2 | |
| Cross-section of connected
  conductors stranded (max) | 2.50 mm2 | |
| Degree of protection | IP 20 | |
| Range of ambient temperatures
  (min/max) | -40 / 70 °C | |
| According to standard | EN 61643-21+A1,A2:2013, IEC
  61643-21+A1,A2:2012 | |
| ETIM Class | EC001625 | |
| Plug module | BDG-006-V/1-0 | |
| Customs tariff number | 85363010 | |
| EAN | 8595090564690 | 
Dimensions:
Lightning current arrester replacement module for 2-core signalling lines, 6 V DC, max. 2 A
Related Product
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.
Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..
Replacement module for FLP-PV700 V/U.
Replacement module for FLP-PV700 V/U.Specifications: Parameter name ..
Replacement module for SLP-PV500 V/U.
Replacement module for SLP-PV1000 V/Y (S).Specifications: Parameter name ..