• Lightning current arrester , replacement module, 2-core high-speed shielding signalling lines, 24 V DC, max. 1 A

Pluggable module, coupling impedance (R – resistance), line separated from protective earth via GDT.

  • Lightning current arrester with coarse and fine surge protection of 2-core high-speed signalling lines.
  • Installation at the boundary of LPZ 0 and LPZ 1 zones or higher, at the line entry into building and also installation close to protected device.
  • For protection of telecommunication lines (version BDGHF-230) and interfaces of I&C, MaR systems, electronic security and fire detection systems, etc. (mainly for RS-485, PROFIBUS interfaces) against surge voltage.
  • Coarse and fine surge protection (core – core, GND) in differential mode and coarse surge protection in common mode (line – PE).


Specifications:


Parameter name

Parameter value

Type of SPD

D1,C2

Location of SPD

ST 1+2+3

Mounting

DIN rail 35 mm

Nominal voltage

Un

24 V DC

Maximum operating voltage

Uc

25.00 V AC

Maximum operating voltage

Uc

36.00 V DC

Nominal load current

IL

1.000 A

Treshold frequency core-core

f

70.00 MHz

Serial resistance per core

R

0.80 Ω

C2 nominal discharge current (8/20 µs) GND-PE

In

10.00 kA

C2 nominal discharge current (8/20 µs) per core

In

10.00 kA

C2 total discharge current (8/20 µs) cores-PE

ITotal

20.00 kA

C3 nominal discharge current (10/1000 µs) core-PE

ISM

10 A

C3 nominal discharge current (10/1000 µs) core-core

ISM

10 A

C3 voltage protection level mode GND-PE at 1 kV/µs

Up

550.00 V

C3 voltage protection level mode core-GND at 1 kV/µs

Up

48.00 V

C3 voltage protection level mode core-core at 1 kV/µs

Up

48 V

Response time core-core

ta

1 ns

Response time core-GND

ta

1 ns

Response time GND-PE

ta

100 ns

Connection (input - output)

terminals-terminals

Cross-section of connected conductors solid (min)

0.14 mm2

Cross-section of connected conductors solid (max)

4.00 mm2

Cross-section of connected conductors stranded (min)

0.14 mm2

Cross-section of connected conductors stranded (max)

2.50 mm2

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 70 °C

According to standard

EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012

ETIM Class

EC001625

Plug module

BDMHF-024-V/1-0

Customs tariff number

85363010

EAN

8595090565536


Dimensions:



Replacement module: BDMHF-024-V/1-0

Datasheet:

     BDMHF-024-V/1-FR1

Write a review

Note: HTML is not translated!
Captcha

Lightning current arrester , replacement module, 2-core high-speed shielding signalling lines, 24 V DC, max. 1 A

* Required fields


Terms & Conditions

All prices are subject to confirmation and exclude applicable taxes unless otherwise stated. Payment terms are as agreed in the quotation or invoice. Orders will be processed only after payment confirmation or receipt of an approved purchase order, where applicable. Dafnia reserves the right to modify product pricing, availability, and payment terms without prior notice.


Related Product

Heavy Duty 400V Surge Protected Office Power Outlet Strip

Heavy Duty 400V Surge Protected Office Power Outlet Strip

Specifications: Combi ON-OFF switch with integrated signal light Optimal user protection ..

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 100 V DC.

Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.

Isolation spark gap, 50 kA (10/350 µs), screws, withstand voltage 50 V DC.

Two M8 bolts with nuts.Encapsulated high-performance isolating spark gap.For indirect connection (ea..

Replacement module for FLP-PV700 V/U.

Replacement module for FLP-PV700 V/U.

Replacement module for FLP-PV700 V/U.Specifications:Parameter name Parameter valu..