• Surge protection for two 1-core signalling networks, terminal block with screw terminals, 12 V DC, max. 0.5 A

Coupling impedance (resistance), screw terminals

  • Coarse and fine surge protection for two 1-core signalling networks
  • Installation close to protected equipment
  • For protection of communication interfaces and control circuits of I&C, electronic security and fire detection systems, etc. against impact of surge voltage
  • Coarse and fine surge protection in common mode (core – PE)


Specifications:


Parameter name

Parameter value

Type of SPD

C2,C3

Location of SPD

ST 2+3

Mounting

DIN rail 35 mm

Nominal voltage

Un

12 V DC

Maximum operating voltage

Uc

11.00 V AC

Maximum operating voltage

Uc

16.00 V DC

Nominal load current

IL

0.500 A

Treshold frequency core-core

f

2.00 MHz

Serial resistance per core

R

1.60 Ω

D1 impulse discharge current (10/350 µs) per core

Iimp

0.50 kA

D1 total discharge current (10/350 µs) cores-PE

ITotal

1.00 kA

C2 nominal discharge current (8/20 µs) per core

In

5.00 kA

C2 total discharge current (8/20 µs) cores-PE

ITotal

10.00 kA

C2 voltage protection level mode core-PE at In

Up

40 V

C3 voltage protection level mode core-PE at 1 kV/µs

Up

20 V

Response time core-PE

ta

1 ns

Connection (input - output)

terminals-terminals

Cross-section of connected conductors solid (min)

0.14 mm2

Cross-section of connected conductors solid (max)

4.00 mm2

Cross-section of connected conductors stranded (min)

0.14 mm2

Cross-section of connected conductors stranded (max)

2.50 mm2

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 70 °C

According to standard

EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012

ETIM Class

EC001625

Customs tariff number

85363010

EAN

8595090551447


Dimensions:



Write a review

Note: HTML is not translated!
Captcha

Surge protection for two 1-core signalling networks, terminal block with screw terminals, 12 V DC, max. 0.5 A

0 reviews / Write a review

* Required fields



Related Product

AC diverter ,for suppression of AC voltage

AC diverter ,for suppression of AC voltage

SPD for Cathodic Corrosion Protection System.Combines an AC current diverter and a SPD in one enclos..

Digital tester for status monitor of SPDs

Digital tester for status monitor of SPDs

Measurement of insulation resistance. It can be used to provide a more accurate imagine of the SPD s..

Automatic VLD class 2 tester

Automatic VLD class 2 tester

Portable automatic tester of VLD class 2.Fully automatic measurement.Measurement of Non-triggering v..

Voltage limiting device, VLD of class 2.2, type VLD-O+F

Voltage limiting device, VLD of class 2.2, type VLD-O+F

Voltage limiting device, VLD of class 2.2, type VLD-O+F, limiting of occurrence non-permissible touc..