• Surge protection for 2-core signalling lines, installation close to protected equipment, 24 V DC, max. 0,5 A.

Coupling impedance (R – resistance).

  • Coarse and fine surge protection for 2-core signalling lines.
  • Installation close to protected equipment.
  • For protection of communication interfaces of I<(>&<)>C, electronic security and fire detection systems, etc. (mainly for RS-485 interfaces) against impact of surge voltage.
  • Coarse and fine surge protection in differential mode (core – core) and common mode (core – PE).


Specifications:


Parameter name

Parameter value

Type of SPD

D1,C1,C2,C3,B2

Location of SPD

ST 2+3

Mounting

DIN rail 35 mm

Nominal voltage

Un

24 V DC

Maximum operating voltage

Uc

25.00 V AC

Maximum operating voltage

Uc

36.00 V DC

Nominal load current

IL

0.500 A

Treshold frequency core-core

f

4.00 MHz

Serial resistance per core

R

1.00 Ω

D1 total discharge current (10/350 µs) cores-PE

ITotal

1.00 kA

C1 voltage protection level mode core-core

Up

65.00 V

C1 test voltage mode core-core

UOC

4.00 kV

C1 voltage protection level mode core-PE

Up

65.00 V

C1 test voltage mode core-PE

UOC

4.00 kV

B2 voltage protection level mode core-core

Up

50.00 V

B2 test voltage mode core-core

UOC

1.00 kV

B2 voltage protection level mode core-PE

Up

50.00 V

B2 test voltage mode core-PE

UOC

1.00 kV

C2 nominal discharge current (8/20 µs) per core

In

10.00 kA

C2 total discharge current (8/20 µs) cores-PE

ITotal

20.00 kA

C3 nominal discharge current (10/1000 µs) core-PE

ISM

10 A

C3 nominal discharge current (10/1000 µs) core-core

ISM

10 A

C2 voltage protection level mode core-PE at In

Up

75 V

C2 test voltage mode core-PE

UOC

20.00 kV

C2 voltage protection level mode core-core at In

Up

75 V

C2 test voltage mode core-core

UOC

20.00 kV

C3 voltage protection level mode core-PE at 1 kV/µs

Up

50 V

C3 voltage protection level mode core-core at 1 kV/µs

Up

50 V

Response time core-core

ta

1 ns

Response time core-PE

ta

1 ns

Connection (input - output)

terminals-terminals

Cross-section of connected conductors solid (max)

4.00 mm2

Cross-section of connected conductors stranded (max)

4.00 mm2

Degree of protection

IP 20

Range of ambient temperatures (min/max)

-40 / 80 °C

Humidity

5 - 95 %

According to standard

EN 61643-21+A1,A2:2013, IEC 61643-21+A1,A2:2012

ETIM Class

EC001625

Customs tariff number

85363010

EAN

8595090567288



Dimensions:




Write a review

Note: HTML is not translated!
Captcha

Surge protection for 2-core signalling lines, installation close to protected equipment, 24 V DC, max. 0,5 A.

0 reviews / Write a review

* Required fields



Related Product

Surge protection for small-voltage AC/DC power supply networks with RFi filter, up to 24 V AC or DC

Surge protection for small-voltage AC/DC power supply networks with RFi filter, up to 24 V AC or DC

Visual fault singallingSurge protection with integrated RFi filterInstallation to LV installations, ..

Surge protection for small-voltage AC/DC power supply networks with RFi filter, remote fault signalling, up to 12 V AC or DC

Surge protection for small-voltage AC/DC power supply networks with RFi filter, remote fault signalling, up to 12 V AC or DC

Visual and remote fault signallingSurge protection with integrated RFi filterInstallation to LV inst..

Surge protection for small-voltage AC/DC power supply networks with RFi filter, up to 12 V AC or DC

Surge protection for small-voltage AC/DC power supply networks with RFi filter, up to 12 V AC or DC

Visual fault singallingSurge protection with integrated RFi filterInstallation to LV installations, ..

Surge protection for ELV of AC/DC power supply networks, up to 48 V DC

Surge protection for ELV of AC/DC power supply networks, up to 48 V DC

Visual fault singallingSurge protection for all types of LV electric and electronic equipments again..